PRODUCT DESIGN
HKR ELECTRICAL DATA
All wires and overcurrent protection devices are sized for use with electric heaters only and without
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See
PACKAGE UNIT SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent pro-
tection during refrigeration cycle.
WARNING
WARNING
IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.
GPH13[24-60]M41*
Supply Votage
240 230 220 210 208
Correction Factor
1.0 0.93 0.85 0.78 0.76
Multiply rated kW by correction factor to get actual kW
Heating kW Correction Factor
Maximum Maximum
Overcurrent Overcurrent
Protection (amps) Protection (amps)
at 208 / 240V at 208 / 240V
GPH1324M41*
HKR05A,CA
24 / 27 30 / 30 ---- ---- 4.75 / 16,200
HKR08A,CA
33 / 28 40 / 40 ---- ---- 7.00 / 23,800
HKR10A,CA 45 / 51 60 / 60 ---- ---- 9.50 / 32,400
GPH1330M41*
HKR05A,CA 24 / 27 30 / 30 -- -- 4.75 / 16,200
HKR08A,CA 34 / 39 40 / 40 -- -- 7.0 / 23,800
HKR10A,CA 45 / 52 60 / 60 -- -- 9.5 / 32,400
HKR15A,CA 45 / 52 60 / 60 22 / 25 30 / 30 14.25 / 48,600
GPH1336M41*
HKR05A,CA
24 / 27 30 / 30 ---- ---- 4.75 / 16,200
HKR08A,CA
34 / 39 40 / 40 ---- ---- 7.00 / 23,800
HKR10A,CA
45 / 52 60 / 60 ---- ---- 9.50 / 32,400
HKR15A,CA 45 / 52 60 / 60 22 / 25 30 / 30 14.25 / 48,600
GPH1342M41*
HKR05A,CA 24 / 27 30 / 30 -- -- 4.75 / 16,200
HKR08A,CA 34 / 39 40 / 40 -- -- 7.0 / 23,800
HKR10A,CA 45 / 52 60 / 60 -- -- 9.5 / 32,400
HKR15A,CA 45 / 52 60 / 60 22 / 25 30 / 30 14.25 / 48,600
GPH1348M41*
HKR05A,CA
25 / 28 30 / 30 ---- ---- 4.75 / 16,200
HKR08A,CA
34 / 40 40 / 40 ---- ---- 7.00 / 23,800
HKR10A,CA
46 / 53 60 / 60 ---- ---- 9.50 / 32,400
HKR15A,CA
46 / 52 60 / 60 22 / 25 30 / 30 14.25 / 48,600
HKR20A,CA 46 / 52 60 / 60 43 / 49 60 / 60 19.50 / 66,500
GPH1360M41*
HKR05A,CA
26 / 30 30 / 30 ---- ---- 4.75 / 16,200
HKR08A,CA
36 / 40 40 / 40 ---- ---- 7.00 / 23,800
HKR10A,CA
48 / 54 60 / 60 ---- ---- 9.50 / 32,400
HKR15A,CA
48 / 54 60 / 60 22 / 25 30 / 30 14.25 / 48,600
HKR20A,CA 48 / 54 60 / 60 43 / 49 60 / 60 19.50 / 66,500
Actual
kW & BTU
at 240V
Minimum Circuit
Ampacity
at 208 / 240V
Minimum Circuit
Ampacity
at 208 / 240V
Circuit #1 Circuit #2