Goodman Mfg GSC13 Air Conditioner User Manual


 
SS-GSC13 www.goodmanmfg.com 3
Product SPecificationS
SpeCifiCAtionS
GSC13
0181G*
GSC13
0241F*
GSC13
0301E*
GSC13
0361G*
GSC13
0421C*
GSC13
0481C*
GSC13
0601D*
Cooling Capacities
Tonnage 2 3 4 5
Decibels 76 76 72 75 76 76 77
Compressor
RLA 6.8 10.8 13.5 13.4 15.4 19.2 21.8
LRA 40 56 68 74 87 112 137
Condenser Fan Motor
Horsepower 1/8 1/8 1/8 1/6 ¼ ¼ ¼
FLA 0.65 0.65 0.7 1.1 1.5 1.5 1.5
Refrigeration System
Refrigerant Line Size
Liquid Line Size (“O.D.) ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon Line Size (“O.D.) ¾" ¾" ¾" ⅞" 1⅛" 1⅛" 1⅛"
Refrigerant Connecon Size
Liquid Valve Size (“O.D.) ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon Valve Size (“O.D.) ³ ¾" ¾" ¾" ¾" ³ ¾" ³ ⅞" 4 ⅞" 4
Valve Type Sweat Sweat Sweat Sweat Sweat Sweat Sweat
Refrigerant Charge 87 77 66 77 108 128 118
Electrical Data
AC Volts-Hz 208-230/ 60 208/230-60 208/230-60 208/230-60 208/230-60 208/230-60 208/230-60
Min. Circuit Ampacity¹ 9.2 14.2 17.6 17.9 20.8 25.5 28.8
Max. Overcurrent Device² 15 25 30 30 35 40 50
Min / Max Volts 197/253 197/253 197/253 197/253 197/253 197/253 197/253
Electrical Conduit Size ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾"
Equipment Weight (lbs) 116 116 142 141 141 176 207
Ship Weight (lbs) 130 130 159 159 159 194 225
¹ Wire size should be determined in accordance with Naonal Electrical Codes; extensive wire runs will require larger wire sizes
² Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
³ Installer will need to supply ¾” to ⅞” adapters for sucon line connecons.
Installer will need to supply ⅞” to 1⅛” adapters for sucon line connecons.
Notes
Always check the S&R plate for electrical data on the unit being installed.
Charge with refrigerant charge listed on S&R plate; 15’ of ⅜” line included in this charge.
System charge must be adjusted per Installaon Instrucons Final Charge Procedure.