COOLING PERFORMANCE DATA
CKF24-2*
MODEL: CKF24-2* / A24-00-2RA COOLING OPERATION
Outdoor Ambient Temperature
65°F 75°F 85°F 95°F 105°F 115°F 118°F 125°F
Entering Indoor Wet Bulb Temperature
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 53 67 71 59 63 67 71
MBh 23.6 24.5 26.8 - 23.1 23.9 26.2 - 22.5 23.4 25.6 - 21.6 22.3 24.5 - 20.0 20.8 22.8 - 18.5 19.2 21.1 - 17.3 18.0 19.7 - 16.8 17.4 19.1 -
S/T 0.69 0.57 0.40 - 0.71 0.59 0.41 - 0.73 0.61 0.42 - 0.77 0.64 0.44 - 0.81 0.68 0.47 - 0.82 0.69 0.48 - 0.84 0.70 0.49 - 0.85 0.71 0.49 -
DT 18 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 18 16 12 - 17 15 11 - 16 14 11 - 16 14 11 -
816 KW 2.03 2.08 2.15 - 2.20 2.25 2.32 - 2.35 2.40 2.48 - 2.50 2.55 2.64 - 2.60 2.66 2.76 - 2.70 2.76 2.86 - 2.74 2.80 2.90 - 2.75 2.82 2.91 -
AMPS 9.8 10.1 10.4 - 10.6 10.8 11.1 - 11.4 11.6 12.0 - 12.1 12.4 12.8 - 12.8 13.1 13.5 - 13.5 13.8 14.3 - 14.0 14.3 14.8 - 14.2 14.5 15.0 -
HI PR 155 167 177 - 174 188 198 - 198 213 225 - 226 243 257 - 254 273 289 - 281 302 319 - 298 321 339 - 305 329 347 -
LO PR 56 60 65 - 59 63 69 - 61 65 71 - 65 69 75 - 68 72 79 - 70 74 81 - 71 76 83 - 72 76 83 -
MBh 23.3 24.1 26.4 - 22.7 23.6 25.8 - 22.2 23.0 25.2 - 21.2 22.0 24.1 - 19.8 20.5 22.4 - 18.3 18.9 20.7 - 17.1 17.7 19.4 - 16.6 17.2 18.8 -
S/T 0.66 0.55 0.38 - 0.68 0.57 0.39 - 0.70 0.58 0.40 - 0.74 0.61 0.43 - 0.78 0.65 0.45 - 0.79 0.66 0.46 - 0.80 0.67 0.47 - 0.81 0.68 0.47 -
DT 19 17 13 - 20 17 13 - 20 17 13 - 20 17 13 - 19 17 13 - 18 16 12 - 17 15 11 - 17 15 11 -
70 730 KW 2.02 2.07 2.13 - 2.19 2.24 2.31 - 2.33 2.38 2.46 - 2.48 2.54 2.62 - 2.59 2.65 2.74 - 2.68 2.74 2.84 - 2.72 2.78 2.88 - 2.74 2.80 2.90 -
AMPS 9.8 10.0 10.3 - 10.5 10.7 11.1 - 11.3 11.6 11.9 - 12.0 12.3 12.7 - 12.7 13.0 13.4 - 13.4 13.7 14.2 - 13.9 14.2 14.7 - 14.1 14.4 14.9 -
HI PR 154 166 175 - 173 186 197 - 197 212 224 - 224 241 255 - 252 271 287 - 279 300 317 - 296 319 336 - 303 326 345 -
LO PR 56 59 65 - 59 62 68 - 61 65 71 - 64 68 74 - 67 71 78 - 70 74 81 - 71 75 82 - 71 76 83 -
MBh 22.1 22.9 25.1 - 21.6 22.4 24.5 - 21.1 21.9 23.9 - 20.2 20.9 22.9 - 18.8 19.5 21.3 - 17.4 18.0 19.7 - 16.2 16.8 18.4 - 15.7 16.3 17.9 -
S/T 0.63 0.53 0.36 - 0.65 0.55 0.38 - 0.67 0.56 0.39 - 0.70 0.59 0.41 - 0.75 0.62 0.43 - 0.75 0.63 0.44 - 0.77 0.64 0.45 - 0.78 0.65 0.45 -
DT 20 17 13 - 20 17 13 - 20 17 13 - 20 18 13 - 20 17 13 - 19 16 12 - 18 15 12 - 17 15 11 -
644 KW 1.99 2.03 2.10 - 2.15 2.20 2.27 - 2.29 2.34 2.42 - 2.44 2.49 2.58 - 2.54 2.60 2.69 - 2.64 2.70 2.79 - 2.67 2.73 2.83 - 2.69 2.75 2.85 -
AMPS 9.6 9.8 10.1 - 10.3 10.6 10.9 - 11.1 11.4 11.7 - 11.8 12.1 12.5 - 12.5 12.8 13.2 - 13.2 13.5 13.9 - 13.7 14.0 14.4 - 13.9 14.2 14.6 -
HI PR 151 163 172 - 170 183 193 - 193 208 219 - 220 236 250 - 247 266 281 - 273 294 310 - 290 312 330 - 297 320 338 -
LO PR 54 58 63 - 58 61 67 - 60 64 69 - 63 67 73 - 66 70 76 - 68 72 79 - 69 74 80 - 70 74 81 -
MBh 24.0 24.7 26.8 28.7 23.5 24.2 26.1 28.1 22.9 23.6 25.5 27.4 21.9 22.6 24.4 26.2 20.4 21.0 22.7 24.4 18.9 19.4 21.0 22.6 17.6 18.1 19.6 21.1 17.1 17.6 19.1 20.5
S/T 0.78 0.70 0.53 0.3 0.81 0.72 0.55 0.4 0.83 0.74 0.56 0.4 0.87 0.78 0.59 0.4 0.93 0.83 0.63 0.4 0.94 0.84 0.63 0.4 0.95 0.85 0.65 0.4 0.96 0.86 0.65 0.4
DT 21 19 16 11 21 20 16 11 21 20 16 11 22 20 16 11 21 20 16 11 20 18 15 10.4 19 17 14 9.9 19 17 14 9.7
816 KW 2.05 2.10 2.17 2.2 2.22 2.27 2.34 2.4 2.37 2.42 2.50 2.6 2.52 2.57 2.66 2.8 2.63 2.69 2.78 2.9 2.72 2.79 2.88 3.0 2.76 2.83 2.92 3.0 2.78 2.84 2.94 3.0
AMPS 9.9 10.1 10.4 10.8 10.7 10.9 11.2 11.6 11.5 11.7 12.1 12.5 12.2 12.5 12.9 13.3 12.9 13.2 13.6 14.1 13.6 14.0 14.4 14.9 14.1 14.4 14.9 15.4 14.3 14.6 15.1 15.6
HI PR 157 169 178 186.0 176 189 200 208.7 200 216 228 237.4 228 245 259 270.3 257 276 292 304.1 284 305 322 336.0 301 324 342 356.9 309 332 351 365.8
LO PR 57 60 66 70.0 60 64 69 73.9 62 66 72 76.8 65 69 76 80.7 68 73 79 84.6 71 75 82 87.5 72 76 83 88.9 72 77 84 89.5
MBh 23.7 24.4 26.4 28.3 23.1 23.8 25.8 27.6 22.6 23.2 25.2 27.0 21.6 22.2 24.1 25.8 20.1 20.7 22.4 24.0 18.6 19.1 20.7 22.2 17.4 17.9 19.4 20.8 16.8 17.3 18.8 20.2
S/T 0.75 0.67 0.51 0.3 0.78 0.69 0.52 0.3 0.79 0.71 0.54 0.3 0.84 0.75 0.57 0.4 0.89 0.79 0.60 0.4 0.90 0.80 0.61 0.4 0.91 0.82 0.62 0.4 0.92 0.82 0.62 0.4
DT 22 21 17 12 23 21 17 12 23 21 17 12 23 21 17 12 22 21 17 12 21 19 16 10.9 20 18 15 10.4 20 18 15 10.2
75 730 KW 2.04 2.08 2.15 2.2 2.21 2.25 2.33 2.4 2.35 2.40 2.49 2.6 2.50 2.56 2.65 2.7 2.61 2.67 2.76 2.9 2.71 2.77 2.86 3.0 2.74 2.81 2.91 3.0 2.76 2.82 2.92 3.0
AMPS 9.9 10.1 10.4 10.7 10.6 10.8 11.1 11.5 11.4 11.7 12.0 12.4 12.1 12.4 12.8 13.2 12.9 13.1 13.6 14.0 13.6 13.9 14.3 14.8 14.0 14.3 14.8 15.3 14.2 14.6 15.0 15.5
HI PR 156 168 177 184.7 175 188 199 207.3 199 214 226 235.7 227 244 257 268.5 255 274 290 302.0 282 303 320 333.7 299 322 340 354.4 306 330 348 363.2
LO PR 56 60 65 69.5 59 63 69 73.4 62 66 72 76.3 65 69 75 80.1 68 72 79 84.0 70 75 82 86.9 71 76 83 88.3 72 76 83 88.9
MBh 22.5 23.1 25.0 26.9 22.0 22.6 24.5 26.3 21.4 22.1 23.9 25.6 20.5 21.1 22.9 24.5 19.1 19.6 21.3 22.8 17.6 18.2 19.7 21.1 16.5 17.0 18.4 19.7 16.0 16.5 17.8 19.1
S/T 0.72 0.64 0.49 0.3 0.74 0.66 0.50 0.3 0.76 0.68 0.52 0.3 0.80 0.72 0.54 0.3 0.85 0.76 0.57 0.4 0.86 0.77 0.58 0.4 0.88 0.78 0.59 0.4 0.88 0.79 0.60 0.4
DT 23 21 17 12 23 21 18 12 23 21 18 12 23 22 18 12 23 21 17 12 22 20 16 11.3 21 19 16 10.7 20 19 15 10.5
644 KW 2.01 2.05 2.12 2.2 2.17 2.22 2.29 2.4 2.31 2.36 2.44 2.5 2.46 2.52 2.60 2.7 2.57 2.63 2.72 2.8 2.66 2.72 2.81 2.9 2.70 2.76 2.85 3.0 2.71 2.78 2.87 3.0
AMPS 9.7 9.9 10.2 10.6 10.4 10.6 11.0 11.3 11.2 11.5 11.8 12.2 11.9 12.2 12.6 13.0 12.6 12.9 13.3 13.8 13.3 13.6 14.1 14.6 13.8 14.1 14.5 15.1 14.0 14.3 14.7 15.3
HI PR 153 164 174 181.0 171 184 195 203.1 195 210 221 231.0 222 239 252 263.1 250 269 284 296.0 276 297 314 327.0 293 315 333 347.3 300 323 341 356.0
LO PR 55 59 64 68.1 58 62 68 71.9 60 64 70 74.8 63 68 74 78.5 67 71 77 82.3 69 73 80 85.1 70 74 81 86.5 70 75 82 87.1
Shaded area is ACCA (TVA) conditions IDB: Entering Indoor Dry Bulb Temperature KW=Total system pow er AMPS=outdoor unit amps (comp.+fan)
High and low pressures are measured at the liquid and suction service valves.
EXPANDED PERFORMANCE DATA