Product SPecificationS
Product SPecificationS
SpecificationS
GPC14
24H41C*
GPC14
24H41D*
GPC14
30H41C*
GPC14
30H41D*
GPC14
36H41C*
GPC14
36H41D*
Cooling Capacity
Cooling Capacity (BTU/h) 23,600 23,600 28,400 28,400 35,600 35,600
Sensible BTU/h 17,700 17,700 21,600 21,600 27,100 27,100
SEER / EER 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0
Decibels 76 76 76 76 78 78
AHRI Numbers
5732583 6892353 5677886 6892355 5677887 6892357
Evaporator Motor
Type EEM EEM EEM EEM EEM EEM
Wheel (D x W) 10 x 8 10 x 8 10 x 8 10 x 8 10 x 8 10 x 8
Cooling CFM 875 875 1,050 1,050 1,200 1,200
Fan-Only CFM 800 800 950 950 1,100 1,100
RLA 1.5 1.5 1.86 1.86 1.86 1.86
No. of Speeds 5 5 5 5 5 5
Horsepower - RPM ½ - 1050 ½ - 1050 ½ - 1050 ½ - 1050 ½ - 1050 ½ - 1050
Evaporator Coil
Face Area (²) 4.66 4.66 5.25 5.25 5.25 5.25
Rows Deep/ Fins per Inch 3/ 16 3/ 16 3/ 16 3/ 16 3/ 14 3/ 14
Indoor Orice Size 0.057 0.057 0.062 0.062 0.068 0.068
Filter Size (") 20 x 20 x 1 20 x 20 x 1 20 x 25 x 1 20 x 25 x 1 25 x 25 x 1 25 x 25 x 1
All-aluminum coil X X X X X X
Drain Size (NPT) ¾" ¾" ¾" ¾" ¾" ¾"
Refrigerant Charge (oz.) 60 60 61 61 65 65
Condenser Fan / Coil
Horsepower - RPM 1/6 - 815 1/6 - 815 1/6 - 815 1/6 - 815 ¼ - 830 ¼ - 830
RLA/LRA 1.1 / 1.7 1.1 / 1.7 1.1 / 1.7 1.1 / 1.7 1.5 / 3.0 1.5 / 3.0
Fan Diameter/ # Fan Blades 22 / 2 22 / 2 22 / 2 22 / 2 22 / 3 22 / 3
Face Area (²) 12.3 12.3 12.3 12.3 12.3 12.3
Rows Deep/ Fins per Inch 1 / 26 1 / 26 1 / 26 1 / 26 1 / 26 1 / 26
Compressor
Quanty / Type 1 / Rotary 1 / Rotary 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll
Stage Single Single Single Single Single Single
Compressor RLA/LRA 7.7/37 7.7/37 12.8 / 64 12.8 / 64 16.7 / 79 16.7 / 79
Electrical Data
Voltage-Phase (60 Hz) 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1
Indoor Blower FLA 1.5 3.8 1.86 3.8 1.86 3.8
Outdoor Fan RLA 1.1 1.1 1.1 1.1 1.5 1.5
Total Unit Amps 10.3 12.6 15.76 17.7 20.06 22
Min. Circuit Ampacity¹ 12.2 15 19 21 24.2 26
Max. Overcurrent Protecon (amps)² 15 20 30 30 40 40
Ship Weight (lbs) 305 305 310 310 315 315
Operating Weight (lbs) 310 310 315 315 320 320
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.