Goodman Mfg 2- to 5-Tone Packaged Air Conditioner Air Conditioner User Manual


 
18 www.goodmanmfg.com SS-GPC14H
SS-GPC14H www.goodmanmfg.com 19
Product SPecificationS
Product SPecificationS
Heat kit eleCtriCal data (Blower only, Heat mode)
Model and
Heat Kit Usage
CirCUit #1 CirCUit #2
s
ingle-Point Kit
aCtUal KW /
BtU@ 240V
MCa¹ MoP² MCa¹ MoP²
MCa¹ MoP²
GPC1424H41** 1.9 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 24 / 27 30 / 30 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 33 / 38 40 / 40 7 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 45 / 51 60 / 60 9.5 / 32,400
GPC1424H41D* 1.9 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 29 30 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 41 45 7 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 54 60 9.5 / 32,400
GPC1430H41** 2.3 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 24 / 27 30 / 30 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 34 / 39 40 / 40 7 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 45 / 52 60 / 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 67 / 77 70 / 80 14.25 / 48,600
GPC1430H41D* 2.3 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 29 30 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 41 45 7 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 54 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 79 80 14.25 / 48,600
GPC1436H41** 2.3 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 24 / 27 40 / 40 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 34 / 39 40 / 40 7 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 45 / 52 60 / 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 67 / 77 70 / 80 14.25 / 48,600
GPC1436H41D* 2.3 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 29 40 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 41 45 7 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 54 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 79 80 14.25 / 48,600
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protection Device @ 208 / 240 V
* Revision level that may or may not be designated
C Circuit breaker option
^ Heat Kit requires three-phase power supply
note: HKP-15C* and HKP-20C* replace HKR-15C and HKR-20C respectively to meet new UL1995 requirements.