GE Monogram 2900 Series Air Conditioner User Manual


 
44
Maximum Connected Load
The maximum connected load of a Zoneline
®
unit occurs when the unit is in resistance heating operation. The maximum
amperage shown in the tables below is the combined total of the resistance heater and the indoor fan motor.
230/208-Volt Line Cord Connected Units
Power Connector Kit
RAK3153
RAK4
157
RAK204D15P
RAK3203
RAK4207
RAK204D20P
RAK3303
RAK4307
RAK204D30P
MODEL
NUMBER
230 V 208 V 230 V 208 V 230 V 208 V
AZ29E07DA* 11.5 10.5 15.5 14.1 N/A N/A
AZ29E09DA* 11.5 10.5 15.5 14.1 22.3 20.3
AZ29E12DA* 11.6 10.6 15.5 14.1 22.3 20.3
AZ29E15DA* 11.6 10.6 15.6 14.2 22.4 20.4
AZ39H07DA*
11.5 10.5 15.5 14.1 N/A N/A
AZ39H09DA*
11.5 10.5 15.5 14.1 22.3 20.3
AZ39H12DA*
11.6 10.6 15.5 14.1 22.3 20.3
AZ39H15DA*
11.6 10.6 15.6 14.2 22.4 20.4
AZ58H07DA* 11.5 10.5 15.5 14.1 N/A N/A
AZ58H09DA* 11.5 10.5 15.5 14.1 22.3 20.3
AZ58H12DA* 11.6 10.6 15.5 14.1 22.3 20.3
AZ58H15DA* 11.6 10.6 15.6 14.2 22.4 20.4
*All versions
Electric Heat Amps include electric heater and fan motor current draw.
Values shown in table above are also the total connected loads for units installed with sub-bases.
RAK204D15P — same as RAK3153
RAK204D20P — same as RAK3203
RAK204D30P — same as RAK3303
265-Volt Units
Sub-Base/Power Connector Kit
RAK204E15
RAK5172
RAK5157
RAK204E20
RAK5202
RAK5207
RAK204E30
RAK5302
RAK5307
MODEL
NUMBER
265 V 265 V 265 V
AZ29E07EA 10.2 13.8 N/A
AZ29E09EA* 10.2 13.8 19.6
AZ29E12EA* 10.3 13.8 19.6
AZ29E15EA* 10.3 13.8 19.6
AZ39H07EA*
10.2 13.8 N/A
AZ39H09EA*
10.2 13.8 19.6
AZ39H12EA* 10.3 13.8
19.6
AZ39H15EA* 10.3 13.8
19.6
AZ58H07EA* 10.2 13.8 N/A
AZ58H09EA* 10.2 13.8 19.6
AZ58H12EA* 10.3 13.8 19.6
AZ58H15DA* 10.3 13.8 19.6
*All versions
Electric Heat Amps include electric heater and fan motor current draw.