Friedrich 920-159-01 (10-03) Air Conditioner User Manual


 
4
5
920-159-01 (10-03)
920-159-01 (10-03)
electrical
entrance
control box
Figure 4
Top View
Exterior Wall
Flexible Ductwork
Rigid Ductwor
k
VPAWP1-8/1-14 Wall Plenum
Plenum
VPDP1 drain pan
beneath unit is
required on all
VEA/VHA24 units.
Drain pan must be
installed prior to
chassis installation
Chassis is
shipped with
vibration
isolators
installed
3" Clearance on all
three sides
minimum for
Optional Platform
Field-supplied
Filter (25" x 20")
58"
29"
VPRG4 Access Panel &
Return Air Filter Grille
Po
wer
Disconnect
II. Installation
1) Utility Closet Dimensions
Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 1. Three inches minimum clearance on
three sides of the unit must be allowed for return airow, installation access and service access. See Figures 1 & 2 for clearances and
reference dimensions.
NOTE: Drain pan must be installed in closet prior to chassis
insertion into plenum. See Figure 7 (page 8) for drain pan
installation details.
Vert-I-Pak Chassis 2-ton dimensions:
23" wide x 23" deep x 47 1/4" high.
VPAWP1-8/1-14 Wall Plenum cut-out
dimensions 24 5/8" wide x 30 7/8" high.
VPRG4 Access Panel cutout dimensions:
27" wide by 55 3/4" high.
See Figure 8 (Page 10) for proper
chassis installation.
Figure 3
Typical Utility Closet
Chassis Shown in Closet, on Optional Platform