II. Installation
1) Utility Closet Dimensions
Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 1. Three inches minimum clearance on
three sides of the unit must be allowed for return airow, installation access and service access. See Figures 1 & 2 for clearances and
reference dimensions.
NOTE: Drain pan must be installed in closet prior to chassis
insertion into plenum. See Figure 7 (page 8) for drain pan
installation details.
•
Vert-I-Pak Chassis 2-ton dimensions:
23" wide x 23" deep x 47 1/4" high.
•
VPAWP1-8/1-14 Wall Plenum cut-out
dimensions 24 5/8" wide x 30 7/8" high.
•
VPRG4 Access Panel cutout dimensions:
27" wide by 55 3/4" high.
•
See Figure 8 (Page 10) for proper
chassis installation.