Faber MISTY Indoor Fireplace User Manual


 
UK/IRL
17
UK/IRL
16
4. INSTRUCTIONS FOR INSTALLATION
4.1 Gas connection
1. Installation pipes should be in accordance with BS 6891. Pipe work
from the meter to the appliance must be of adequate size.
2. The complete installation including the meter must be tested for
soundness and purged as described in the above code.
3. A means of isolation must be provide in the supply to facilitate
servicing.
4. The connection should be made in 8 mm copper or similar semi
flexible tube. (max 1 meter). Ensure that the gas pipe does not
interfere with the removal or replacement of the burner tray of the
controls.
5. The gas connection is nut and olive suitable for 8 mm pipe.
4.2 Preparing the appliances Widescreen and Whisper
1. Open the ashtray door by pushing on the right side for the
Silence/Feeling and on the left side for the Whisper. Remove the
frame by loosening the screws A behind the door (see fig. 5).
Lift and pull forward when you take it away.
A
C
B
gas supply routes when fire is fitted in a deep surround
C = Through wall - Pipe must be sleeved and sealed to fire
A & B = Behind surround - Sleeve pipe through surround
inner wall
outer wall
cavity
surround
marble
Example of how terminal position is measured
3.2.2 Using an existing chimney as air inlet
You can connect the appliance onto an existing chimney. The existing
chimney then functions as air supply, where a flexible stainless steel
liner (to BS715) of 100 mm performs the flue function.
Requirements:
- Any existing chimney used as an air supply must only service this
appliance.
- A chimney that has previously been used for solid fuel must be swept
before use.
- The existing chimney needs to be airtight.
- The existing chimney needs to have an opening of
min. 150 x 150 mm.
- The chimney needs to be intact and well looked after.
- Use the adjustable roof-mounted-terminal especially made for this,
and the chimney connection set.
- The minimum distance between two terminals should be at least
450 mm.
fig. 4
fig. 5