Enviro 50-1578 Stove User Manual


 
This unit may be installed in an alcove. Maintain the
clearances to combustibles shown in Figure 4.
Minimum Alcove width 1220mm (48 inches)
Minimum Alcove height 1220mm (48 inches)
Maximum Alcove depth 915mm (36 inches)
Install vent at clearances specified by
the vent manufacturer.
Minimum Width
1220mm (48")
Minimum Height
1220mm (48")
Maximum Depth
915mm (36")
Figure 4: Alcove Clearances.
Back wall
Side wall
Adjacent
wall
100mm
(4")
100mm (4")
200mm
(7
7
/8 inches)
150mm
(6")
Floor Protection
Figure 3: Minimum Clearances to Combustibles for
Freestanding Windsor.
These dimensions are minimum clearances but it
is recommended that you ensure sufficient room
for serving, routine cleaning and maintenance.
Side wall to unit 200mm (7 inches)
Back wall to unit 100mm (4 inches)
Corner to unit 100mm (4 inches)
In Front of unit 800mm (31” inches)
This pellet stove requires floor protection. The
floor protection must be non-combustible,
extending beneath the stove the full width and
depth of the unit including 150mm (6“) in front
for ember protection.
Hearth Pad Size:
Width: 650 mm (25 ”)
Depth: 815mm (32 ”)
Installation
CLEARANCES TO COMBUSTIBLES:
ALCOVE CLEARANCES:
8