Empire Comfort Systems GWT-50-2 Furnace User Manual


 
12426-4-0104 Page 11
THERMOSTAT LOCATION (SG MODELS)
CAUTION — Do not run wire behind ß anges of Header Plate
or in any location where it might be damaged.
Millivolt wall thermostats are specially designed for use on self-
generating systems. They should never be used on line or low
voltage A.C. circuits.
Interior Wall — The thermostat should be installed on an inside
wall away from the furnace but in the same room.
Note: Use 16 gauge wire to prevent excessive loss of milli-
volts.
Proper operation depends on a good pilot ß ame. The ß ame must
cover the top of the thermopile. Cleaning of the pilot oriÞ ce and
burner may be required due to spiders.
System Check (Figure 7)
A millivolt meter is required to check the system. Millivolt
readings should be:
• Across the thermopile terminals, 400-450 millivolts with
thermostat OFF.
• Across the thermopile terminals, 150-250 millivolts with
thermostat ON.
Across the thermostat wires at the valve, less than 30 millivolts
with thermostat ON.
• Across the thermostat wires at the thermostat, less than 5
millivolts with thermostat ON. (Dirty pilot or low pressure
will reduce readings.)
Connect thermostat wires to gas valve as shown in Figure 7.
Figure 7