EMI S2HB Heat Pump User Manual


 
www.enviromaster.com
23
Multi-zone Heat Pump Condensing Units
S2HB dIMEnSIonS And SPEcIfIcAtIonS
NOTE: All EMI products are subject to ongoing development programs so design and
specications may change without notice.
S2HB
ELECTRICAL SPECIFICATIONS
MODEL
(1)
VOLTS/HZ/PHASE
FAN COMPRESSOR 1 COMPRESSOR 2
TOTAL
AMPS
MIN. CIR.
AMPS
(2)
HACR
BRKR
RLA HP RLA LRA RLA LRA
9900 208-230/60/1 1.8 0.33 3.4 23 3.4 23 8.6 9.5 15
2200 208-230/60/1 1.8 0.33 4.3 27 4.3 27 10.4 11.5 15
9200 208-230/60/1 1.8 0.33 3.4 23 4.3 27 9.5 10.6 15
(1) Circuit Designators: 9 = 9,000 Btuh • 2 = 12,000 Btuh (ex. - Model 9200 consists of one 9,000 Btuh compressor and one 12,000 Btuh compressor)
(2) Always refer to the rating plate for Minimum Circuit Ampacity on all multiple compressor units.
S2HB PIPING SPECIFICATIONS
SOUND DATA
SHIPPING
WEIGHT
Model#
Line Sizes
Liquid Suction
dBA Lbs.
9900 1/4” 1/2”
64
159
2200 1/4” 1/2”
65
197
9200 1/4” 1/2”
65
187
Easy access interconnects
on back of unit
44”
38”
15”
Electrical
connections
Front of unit
1/2” Diameter Lag Holes
7”
7”
23.94”
12.44”
3.00”