Emerson Process Management 2051 Carbon Monoxide Alarm User Manual


 
Quick Installation Guide
00825-0100-4101, Rev EA
June 2010
Rosemount 2051
9
STEP 4: CONNECT THE WIRING AND POWER
Use the following steps to wire the transmitter:
1. Remove the housing cover on the FIELD TERMINALS side.
2. Connect the positive lead to the “+” terminal (PWR/COMM) and the negative lead to the
“–” terminal.
Figure 5. 4–20 mA HART Transmitter Wiring Diagrams
Figure 6. 1-5 Vdc HART Low Power Transmitter Wiring
Installation of the transient protection terminal block does not provide transient protection unless the 2051
case is properly grounded.
3. Ensure proper grounding. It is important that the instrument cable shield:
be trimmed close and insulated from touching the transmitter housing.
be connected to the next shield if cable is routed through a junction box.
be connected to a good earth ground at the power supply end.
R
L
250
Power
Supply
Power
Supply
Voltmeter
4101_QIG_RevEA.fm Page 9 Tuesday, June 29, 2010 9:26 AM