Rosemount 2051
19
IECEx Certifications
I7 IECEx Intrinsic Safety
Certification No. IECExBAS08.0045X
Ex ia IIC T4 (–60 T
a
+70 °C)
1180
Special Conditions for Safe Use (X):
When the optional transient protection terminal block is installed, the apparatus is not
capable of withstanding the 500V insulation test required by Clause 6.3.12 of
IEC60079-11. This must be taken into account when installing the apparatus.
E7 IECEx Explosion-Proof (Flame-Proof)
Certification No. IECExKEM08.0024X
Ex d IIC T6 (–50 T
a
65 °C)
Ex d IIC T5 (–50 T
a
80 °C)
1180
Vmax = 42.4 V dc
Special Conditions for Safe Use (X):
1. Appropriate ex d blanking plugs, cable glands, and wiring needs to be suitable for a
temperature of 90 °C.
2. This device contains a thin wall diaphragm. Installation, maintenance and use shall
take into account the environmental conditions to which the diaphragm will be
subjected. The manufacturer’s instructions for maintenance shall be followed in
detail to assure safety during its expected lifetime.
3. The 2051 does not comply with the requirements of IEC 60079-1 Clause 5 for
flameproof joints. Contact Emerson Process Management for information on the
dimensions of flameproof joints.
N7 IECEx Type n
Certification No. IECExBAS08.0046X
Ex nAnL IIC T4 (–40 T
a
+70 °C)
U
i
= 42.4 Vdc max
Special Conditions for Safe Use (X):
When the optional transient protection terminal block is installed, the apparatus is not
capable of withstanding a 500V r.m.s. test to case. This must be taken into account on
any installation in which it is used, for example by assuring that the supply to the
apparatus is galvanically isolated.
Table 3. Input Parameters
U
i
= 30V
I
i
= 200 mA
P
i
= 1.0W
C
i
= 0.012 µF