Emerson Figure i Air Conditioner User Manual


 
Installation
23
Table 18 Electrical data—Quiet-Line models (95°F/35°C) 60Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
208/230-1 208/230-3 460-3 575-3
27 2
FLA 13.0
WSA 16.0
OPD 25
37 3
FLA 18.8 12.3 6.4 5.2
WSA 23.3 15.2 7.8 6.4
OPD 40 25 15 15
42 3.5
FLA 14.8 6.9 5.9
WSA 18.3 8.5 7.3
OPD 30 15 15
67 5
FLA 21.1 10.9 8.8
WSA 25.9 13.4 10.8
OPD 45 20 15
* FLA = Full Load Amps
WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Overcurrent Protection Device (fuse or circuit breaker)
Model # 14, 20 and 96 are not available in Quiet-Line versions.
Table 19 Electrical data—Standard sound and ambient models (95°F/35°C) 50Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1 200/230-3 380/415-3
13 1 FLA 9.9
19 1.5 FLA 10.9
26 2 FLA 12.7 4.9
36 3 FLA 18.4 7.0
41 3.5 FLA 15.3 8.5
66 5 FLA 24.1 13.2
95 8 FLA 20.3
* FLA = Full Load Amps
Table 20 Electrical data—High ambient models (105°F/41°C) 50Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1 200/230-3 380/415-3
13 1 FLA
19 1.5 FLA
26 2 FLA 14.8 6.0
36 3 FLA 20.5 13.1
41 3.5 FLA 19.8 9.6
66 5 FLA 24.2 13.2
95 8 FLA
* FLA = Full Load Amps