Emerson 0016-00 Home Safety Product User Manual


 
- 2 -
< Relay Contacts:
Normally open/normally closed contacts rated for 5 Amperes at 30 Volts DC/ 250
Volts AC
< Current Outputs:
4-20mA DC into a maximum external loop resistance of 600 Ohms at 18-32
Volts DC
< Dimensions:
Refer to Figure 1
< Shipping Weight (approximate):
2 lbs (0.9 kilograms)
< Certification:
CSA, NRTL/C, NEMA 4X certified for hazardous locations
Class 1, Division 1, Groups B, C and D
IEC approval (Class 1, Zone 1 Groups IIB+H2 T5)
< System Sensitivity:
Sensitivity for the standard controller is field adjustable over a range of 8 through
120 counts per second (cps) in increments of 8 cps. The maximum response
distance is achieved at an 8 cps sensitivity setting. For applications involving high
background radiation potential, the system can be de-sensitized by increasing the
count rate required to actuate alarms. The 120 cps setting is the lowest
sensitivity.
< Response Time:
Response to a saturating (high intensity) UV source is typically 10 milliseconds for
the instant alarm outputs and 0.5 seconds for the area alarm outputs when
sensitivity is set for 8 cps and time delay is set for 0.5 seconds (minimum
settings).
Figure 1 - Controller Dimensions
DETECTOR SPECIFICATIONS
< Operating Voltage:
290Vdc ± 3Vdc (provided for controller)