CLEARANCES TO COMBUSTIBLE MATERIALS
It is of utmost importance that the clearances to combustible material mentioned on your wood stove
certification plate be scrupulously respected upon installation.
CLEARANCES
Model Back Wall Side Walls Corners * Height
Baron 2000sp
24" / 610 mm 16" / 406 mm 16" / 406 mm 7' / 2,13 m
Baron 2000sp
with enveloppe
15" / 381 mm
26,5’’ / 673mm 26,5’’ / 673mm 7' / 2,13 m
Compak
16" / 406 mm 16" / 406 mm 16" / 406 mm 7' / 2,13 m
Contempro 1600
12" / 305 mm 24" / 610 mm 15" / 381 mm 7' / 2,13 m
Contempro 2000
12" / 305 mm 24" / 610 mm 15" / 381 mm 7' / 2,13 m
Gemini 1200
16" / 406 mm 16" / 406 mm 16" / 406 mm 7' / 2,13 m
Gemini 1500
16" / 406 mm 16" / 406 mm 16" / 406 mm 7' / 2,13 m
ML
16" / 406 mm 16" / 406 mm 16" / 406 mm 7' / 2,13 m
RC
16" / 406 mm 16" / 406 mm 16" / 406 mm 7' / 2,13 m
Nordic
16" / 406 mm 16" / 406 mm 16" / 406 mm 7' / 2,13 m
Sawman
16" / 406 mm 30" / 762 mm 30" / 762 mm 7' / 2,13 m
Whistler, DLX
16" / 406 mm 16" / 406 mm 16" / 406 mm 7' / 2,13 m
Single Pipe / Double
Pipe
Single Pipe / Double
Pipe
Single Pipe / Double
Pipe
Classic
16" (406mm) / 12" (305mm) 22" (559mm) / 22" (559mm) 11" (279mm) / 11" (279mm) 7' / 2,13 m
* Height, from stove base to ceiling.
You may decrease these clearances by installing heat radiation shields between the walls or the ceiling and
the stove. These heat radiation shields must be installed permanently, and can include sheet metal, a rigid
non-combustible sheet or a masonry wall. The installation standards of such heat radiation shields are listed
on the following page.
IT IS STRICTLY FORBIDDEN TO PLACE WOOD WITHIN THE MINIMUM CLEARANCES.