DMP Electronics Command Processor Panel Home Security System User Manual


 
22
XR10 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
11.10 4-2 Examples
The following examples are the actual event codes a central station would receive. The full report would also include
the account number and checksum.
When the central station receives this event code It means
1A A Fire alarm is being reported on zone 10
2B An Ambush alarm is being reported
FB A battery trouble is being reported
F9 A Trouble is being reported on zone nine
11.11 4-2 Communication Format Configuration
The DMP 4-2 format communicates to the central station as 4-2 with a checksum at 40 pulses per second (pps). The
XR10 panel using 4-2 communication will accept either a 1400Hz or 2300Hz acknowledgment tone (handshake) from
the receiver.
A report format sent to the receiver is defined as follows:
1234 56 7
aaaa f s c
a = account number
f = first digit
s = second digit
c = checksum
11.12 Numeric Pager Message Formats
The following example shows individual page display components:
Pager Display - 00128–20010
00128 = account number
2 = Message ID
0 = Always zero
010 = Zone or area number
Message ID Descriptions
1 = Zone Alarm
2 = Zone Trouble
3 = Areas Arming
4 = Areas Disarming
6 = User Checkin
The examples below show a typical display for each of the pager report options:
Zone Alarm Zone Trouble Areas Arming Areas Disarming User Checkin
00128–10003 00128–20010 00128–30123 00128–40123 00128–60008
Communication Attempts
Only one pager signal is sent to the pager terminal equipment at a time. For each pager message to be sent, the
panel dials the first phone number and follows the steps detailed in the sections 3.19 and 3.20.
11 - APPENDIX
Digital Monitoring Products
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282