7.1 OUTPUT OPTIONS
This function allows you to program the panel's Bell Output functions and certain Output
options. Switched Ground (open collector) outputs are available from the XR10 when using a
4-wire output harness (Model 300 Harness). Refer to the XR10 Installation Guide (LT-0229)
for complete information.
A description of each output option follows:
7.2 BELL CUTOFF TIME
Enter the maximum time the Bell Output remains on. If the Bell Output is manually silenced or
the system is disarmed, the cutoff time is reset. The Bell Cutoff Time can be from 1 to 15
minutes in one minute increments.
Enter zero to provide a continuous bell output.
7.3 AUTOMATIC BELL TEST
When YES is selected, the Bell Output is turned on for two seconds when all areas in the
system are armed. In addition, the Closing Wait feature is activated if Opening/Closing
Reports is YES. See section 5.2.
Closing Wait operation
Closing Wait provides a delay time before a monitored system arms until the panel receives an acknowledgment of
the closing report from the central station receiver. During the delay, the keypad displays DIALING . . .. Once the
closing is acknowledged, the keypad buzzer and the Bell Output sound for two seconds and the keypad displays the
system armed message.
If the closing report is not acknowledged, the keypad buzzer and Bell Output do NOT sound, the keypad displays
LOCAL ALARM ONLY, and the system arms locally.
7.4 BELL ACTION
This option defines the type of Bell Output for zone alarms. (Trouble conditions do not
activate the Bell Output.) There are seven zone types you can program for Bell Output.
For a steady Bell Output, enter S. For a pulsed output, enter P. For no Bell Output, enter N.
Program the bell action for each zone type below:
7.4A FIRE ZONES
Defines Bell Action for Fire Type Zones.
7.4B BURGLARY ZONES
Defines Bell Action for Burglary Type zones. If you select N, Exit Error alarms are not
indicated locally but Exit Error reports are still sent to the receiver. See Appendix section 11.2.
7.4C SUPERVISORY ZONES
Defines Bell Action for Supervisory Type Zones
7.4D PANIC ZONES
Defines Bell Action for Panic Type Zones
7.4E EMERGENCY ZONES
Defines Bell Action for Emergency Type Zones
7.4F AUXILIARY 1 ZONES
Defines Bell Action for Auxiliary 1 Type Zones
7.4G AUXILIARY 2 ZONES
Defines Bell Action for Auxiliary 2 Type Zones
7 - OUTPUT OPTIONS
OUTPUT OPTIONS
BELL CUTOFF: 15
BELL TEST NO
BELL ACTION . . . . .
SUPRVSRY TYPE: N
BURGLARY TYPE: S
PANIC TYPE: N
EMERGNCY TYPE: N
AUXLRY I TYPE: N
FIRE TYPE: P
AUXLRY 2 TYPE: N