XR10 Programming Guide
8.6 ARM AREAS
This option specifies the areas to be armed by the Arming Type Zone. When disarmed, all
areas in the system are disarmed.
PERIMETER/ALL - Specify whether the arming zone arms just the Perimeter (PERIM) or the
Perimeter and Interior areas (ALL) for All/Perimeter systems.
HOME/SLEEP/AWAY - Specify whether the arming zone arms the Perimeter (HOME), the
Perimeter and Interior (SLEEP), or all three areas (AWAY).
Arming zone operation
If a bad (faulted) Priority zone is in the area being armed by an Arming zone, the arming is stopped. If there are no
Priority zones, or they are all in a normal condition, the following applies:
If a non-Priority zone is in a bad condition when an area is armed with a keyswitch on an Arming zone, the arming is
delayed for five seconds. If, during the five second delay, the keyswitch is turned to disarm, the arming is stopped. If
the keyswitch is held in the arming position for the full five seconds, the bad zone is force armed and the area armed.
Momentary keyswitch operation
When the Arming zone changes from normal to short, any armed areas are disarmed. If all areas are disarmed
when the Arming zone is shorted, the panel arms all areas. When the Arming zone changes from normal to open
while any areas are armed, an alarm is indicated and the areas must be disarmed from a keypad. If all areas are
disarmed, only a trouble is indicated.
8.7 NEXT ZONE
When YES is selected, the programming for the zone terminates and the display returns to
ZONE NO: - allowing you to enter a new zone number. To make changes to the Alarm
Action for a zone, answer the NEXT ZONE? prompt with NO. The Alarm Action is then
defined in sections 8.8 through 8.13.
8.8 ALARM ACTION
The Alarm Action section allows you to change or confirm the default alarm characteristics of
a zone type that was selected in section 8.4.
If you selected the non-24 hour zone type Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2,
the Alarm Action programing begins with Disarmed Open.
If you selected the 24 hour zone type Fire, Panic, Emergency, or Supervisory, the Alarm
Action programming begins with Armed Open.
The Fire Verify zone type functions the same as Fire Type, with the following exceptions:
When a Fire Verify zone is placed into shorted condition, the panel performs a Sensor Reset
and does not send a report. If any Fire Verify or Fire zone initiates an alarm within 120
seconds after the reset, an alarm is indicated. If an alarm is initiated after 120 seconds, the
cycle is repeated. If no other Fire Verify or Fire zone is alarmed within 120 seconds, a zone
fault report is sent to the receiver.
8.9 DISARMED OPEN
Defines the action taken by the panel when the zone is opened while the area is disarmed.
There are three actions to define:
Message to Transmit Output Number Output Action
See sections 8.9A to 8.9C. You must also make these selections for the Disarmed Short,
Armed Open, and Armed Short zone conditions.
Press the COMMAND key to continue.
8 - ZONE INFORMATION
ARM AREAS:
PERIM ALL
HOME SLEEP AWAY
NEXT ZN? NO YES
ALARM ACTION . . . .
DISARMED OPEN