Desa (V)T36N SERIES Indoor Fireplace User Manual


 
www.desatech.com
108661-01F
6
Fixed
Closed
Openable
Fixed
Closed
Openable
V
V
V
V
V
V
V
V
X
X
V
X
G
G
J
F
B
B
K
N
H
I
A
N
E
L
D
B
M
A
C
B
V
V
A
G
G
B
TERMINATION CAP
AIR SUPPLY INLET
GAS METER RESTRICTED AREA
(TERMINATION PROHIBITED)
A = clearance above grade, veranda, porch, deck, or balcony
[*12" (30.5 cm) minimum]
B = clearance to window or door that may be opened
[12" (30.5 cm) minimum]
C = clearance to permanently closed window [minimum 12" (30.5 cm)
recommended to prevent condensation on window]
D = vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 24" (61cm) from the
center-line of the terminal [18" (45.7 cm) minimum]
E = clearance to unventilated soffit [12" (30.5 cm) minimum]
F = clearance to outside corner (see below)
G = clearance to inside corner (see below)
H = *not to be installed above a meter/regulator assembly within
36" (91.4 cm) horizontally from the center-line of the regulator
I = clearance to service regulator vent outlet [*72" (182.9 cm)
minimum]
J = clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other fireplace [*12" (30.5 cm)
minimum]
K = clearance to a mechanical air supply inlet [*72" (182.9 cm)
minimum]
L = † clearance above paved side-walk or a paved driveway located on
public property [*84" (213.3 cm) minimum]
M = clearance under veranda, porch, deck [*12" (30.5 cm) minimum ‡]
N = clearance above a roof shall extend a minimum of 24" (61 cm)
above the highest point when it passes through the roof surface and
any other obstruction within a horizontal distance of 18" (45.7 cm)
† vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings*
‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
* as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.
Note: Local codes or regulations may require different clearances
A = 6" (15.2 cm)
Inside Corner
V
B
E
V
B = 6" (15.2 cm)
C = Maximum depth of 48" (121.9 cm) for
recessed location
D = Minimum width for back wall of
recessed location -
Combustible - 38" (96.5 cm)
Noncombustible - 24" (61cm)
E = Clearance from corner in
recessed location-
Combustible - 6" (15.2 cm)
Noncombustible - 2" (5.1 cm)
Outside Corner Recessed Location
G
H
G = 12" (30.5 cm) minimum clearance
Balcony with No Side Wall
V
J
Combustible &
Noncombustible
H = 24" (61 cm)
J = 20" (50.8 cm)
Balcony with Perpendicular Side Wall
C
D
C
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Figure 7 - Minimum Clearances for Termination Cap
LOCATION OF TERMINATION CAP