Desa Vm42eP Indoor Fireplace User Manual


 
www.desatech.com
108796-01L 9
INSTALLING TRANSITION PIPE AND
STARTER COLLAR
The transition pipe and starter collar shown in
Figure 9 are supplied with the replace, unattached
and ready for installation. Remove the starter collar
and set aside. Slide the transition pipe over the vent
collar and attach with a minimum of three screws.
Replace the starter collar over the transition pipe
and attach using four screws located on the leg
stands (ve used on the model M42E). To install
B-vent piping, slide the rst piece of B-vent over
the transition pipe and attach with either a mini-
mum of two screws or other means approved by
the vent manufacturer.
Figure 9 - Installing Transition Pipe and
Starter Collar
B-Vent Piping
Transition Pipe
Starter Collar
Vent Collar
PRE-INSTALLATION
PREPARATION
Continued
VENTING INSTALLATION
A B-type venting system must be connected to the
appliance for venting to the outside of the building.
The following section is provided as a guide to a
standard B-type vent installation.
Standing codes requirements concerning B-type
vent installations may vary within your state,
province or local codes jurisdiction. Therefore,
it is recommended that you check with your
local building codes for specic requirements
or in absence of local codes, follow Section 7.0
of the current National Fuel Gas Code ANSI
Z223.1/NFPA 54 and in Canada with CAN/CGA
B149 for Category I systems using double wall
B-1 vent pipe.
This gas appliance must be vented to the outdoors
only and may not be terminated into an attic space
or into a chimney ue servicing a solid-fuel burn-
ing appliance.
This appliance may be vented through a manufac-
tured chimney system or a masonry chimney using
a B-vent adapter or a chimney liner system if all
are listed, inspected and approved by local codes
and/or building authorities.
The examples shown in Figure 10, page 10 are
typical of most B-vent installations and codes
practices.
Example 1: Shows the minimum allowable sys-
tem height and lateral offset for a 60° degree or
greater inclination. Code species that offsets at
60° degrees or greater are considered horizontal
and must follow the 75% percent rule for lateral
to total vertical system height. Codes also allows
only one offset in the total system when at 60°
degrees or greater. The total vertical height in this
example represents the minimum height of 8 feet
and therefore the allowable lateral is 6 feet when
the 75% percent rule applies. If the lateral length
must exceed 75% then the system must be sized in
accordance with the Category I venting tables.
Example 2: Shows a multiple offset each at 45°
degrees of inclination. Multiple offsets are permit-
ted if they do not exceed 45° degrees of inclination.
The total lengths of the two offsets are not required
to meet the 75% percent allowable rule.
Example 3: Shows a single offset at 45° degrees
of inclination and therefore the lateral length at
10 feet of offset does not have to meet the 75%
percent rule.
In each case the offsets must be supported and
restops must be positioned wherever the vent
must pass through a sub-oor, ceiling joist or
an attic overhang. The vent pipe must terminate
vertically into a listed type vent cap and extend a
sufcient height through an approved roof ash-
ing, roof jack or a roof thimble. At all points the
listed clearances must be maintained.
Vent terminations must be located in accordance
with height and proximity rules of NFPA No. 54 or
CAN/CGA B149. These rules apply to vents at 12
in. diameter or less and require a minimum height
in accordance with the roof pitch and a minimum
of 8 ft. distance from a vertical wall or obstruction
(see Figure 11, page 10).
If venting horizontally through a side wall be-
comes necessary, a listed thimble approved for use
with B-type vent must be used. Check with your
local codes before venting through a side wall.
Some codes areas allow the use of existing B-type
vent systems if the system is at or above the recom-
mended diameter of the ue; in this case 6".