1. Determine the volume of the space (length x
width x height).
Length x Width x Height = _________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room is sup-
plied with grills or openings, add the volume of
these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
____________(volume of space) x 20 =
(Maximum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x
20 = 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances
in the space.
Vent-free appliance _________Btu/Hr
Gas water appliance* _________Btu/Hr
Gas furnace _________Btu/Hr
Vented gas appliance _________Btu/Hr
Gas replace logs _________Btu/Hr
Other gas appliances* +_________Btu/Hr
Total =_________Btu/Hr
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:
Gas water appliance _________Btu/Hr
Vent-free appliance +_________Btu/Hr
Total =_________Btu/Hr
4. Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
___________ Btu/Hr (maximum the space
can support)
____________Btu/Hr (actual amount of
Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the
space can support)
73,000 Btu/Hr (actual amount of
Btu/Hr used)
AIR FOR COMBUSTION
AND VENTILATION
Continued
The space in the previous example is a conned
space because the actual Btu/Hr used is more than
the maximum Btu/Hr the space can support. You
must provide additional fresh air. Your options
are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an
unconned space, remove door to adjoining
room or add ventilation grills between rooms.
See Ventilation Air From Inside Building.
B. Vent room directly to the outdoors. See Ven-
tilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr appliance, if lower
Btu/Hr size makes room unconned.
If the actual Btu/Hr used is less than the
maximum Btu/Hr the space can support, the
space is an unconned space. You will need
no additional fresh air ventilation.
WARNING: If the area in which


     
    



in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section 5.3

VENTILATION AIR

This fresh air would come from an adjoining un-
conned space. When ventilating to an adjoining
unconned space, you must provide two perma-
nent openings: one within 12" of the ceiling and
one within 12" of the oor on the wall connecting
the two spaces (see options 1 and 2, Figure 2 on
page 8). You can also remove door into adjoining
room (see option 3, Figure 2). Follow the National
Fuel Gas Code, ANSI Z223.1/NFPA 54, Section
5.3, Air for Combustion and Ventilation for re-
quired size of ventilation grills or ducts.