Daewoo Split Airconditioning System Air Conditioner User Manual


 
INSTALLATION (CONTINUED)
10
3. Once a smooth match is made, tighten the flare nut
using a wrench. Be very careful not to strip the
threads or flare nut. Repeat this process for the small
and large tubing. When tightening the flare nut, use
another wrench to securely hold the coupler from
twisting and possibly damaging the tubing.
4. Remove the flare nut stoppers from the outdoor
unit’s valves. Connect the larger copper tubing to the
larger valve on the outdoor unit. Connect the smaller
copper tubing to the smaller valve on the outdoor
unit.
5. Perform a leak test on all copper tube connections.
To prevent heat loss and damage to walls from con-
densation, the copper tube connections coming from
the wall must be insulated. Do this by wrapping foam
rubber or equivalent around the connection approxi-
mately 8mm thick so no copper tubing is exposed.
NOTES:
As with all wiring and hookups on this unit, make sure
the AC plug on the indoor unit is unplugged.
• Be very careful not to strip the threads or flare nut.
When insulating the connections, use foam rubber or
equivalent.
1. Connect the drain hose extension to the drain hose
coming from the indoor unit by loosing the clamp on
the extension using a phillips screwdriver, attaching
the hoses together and then tightening the clamp.
2. Run the drain hose, slanted downward, outside. If
the drain pipe is exposed indoors, make sure it is
thoroughly insulated so condensation does not ruin
walls or furniture or come in contact with the AC con-
nection or extension. Also, do not crease or form a
trap in the tubing.
Wall Bracket
Insert Putty
Drain Hose
CONNECTING THE DRAIN HOSE
To connect the drain hose, follow the procedures below: