Crestron electronic 277 Volt Indoor Furnishings User Manual


 
CRESTRON GREEN LIGHT™ Architectural Dimming
Testing
Manual Control
A lighting module can be manually controlled from its front panel.
Switch Function
The GLX-HSW8 is a power switching module that can be used to turn loads on and off.
The GLX-DIM6 and the GLX-DIMFLV8 are dimming modules whose outputs can be set to operate as
dimmable or non-dimmable outputs. The state of each output can be manually controlled from the front panel.
To use a module’s switch function:
Ensure that the output’s mode switch is set to NON-DIM (GLX-DIM6 and GLX-DIMFLV8 only).
The DIM LED will be off.
Press the S button to turn the output on. The corresponding ON LED illuminates and the output state
is shown on the NET ID display (“On” for on) for two seconds after the button is released.
Press the T button to turn the output off. The corresponding ON LED extinguishes and the output
state is shown on the NET ID display (“oF” for off) for two seconds after the button is released.
NOTE: The control system program may change the settings if the Override mode is not enabled.
Dimming Function (GLX-DIM6 and GLX-DIMFLV8 Only)
The lighting level of each of the outputs can be manually controlled from the front panel.
Ensure that the output’s mode switch is set to DIM (GLX-DIM6 and GLX-DIMFLV8 only).
Press the S button to turn the output on (100%). The corresponding ON and DIM LEDs illuminate
and the output state is shown on the NET ID display (“On” for on) for two seconds after the button is
released.
Press the T button to turn the output off. The corresponding ON LED extinguishes and the output
state is shown on the NET ID display (“oF” for off) for two seconds after the button is released.
To ramp the lighting level up or down (until it reaches 100% or turns off), press and hold the output’s
S or T button. The corresponding ON LED illuminates while the load is ON. The DIM LED
illuminates while the output level is less than 100%. The output level is shown on the NET ID display
as a percentage (01-99, “oF” for off, or “On” for on) for two seconds after the button is released.
NOTE: The control system program may change the settings if the Override mode is not enabled.
Override Mode
The Override mode overrides the control system program and sets all of the output states to the stored override
values. For instructions on saving override settings, refer to “Save Override Settings” on page 12.
To enable Override mode, press and release the OVR button. The OVR LED flashes slowly.
NOTE: If the Override mode was enabled from an external device (i.e. a contact closure is present on the
OVERRIDE terminals), the OVR LED will flash quickly. Pressing the OVR button has no effect.
To disable Override mode, press the OVR button again. The OVR LED extinguishes and the outputs return to the
states set by the control system program.
NOTE: If override states have not been stored, the factory default override state is all loads on.
Installation Guide – DOC. 6688A CRESTRON GREEN LIGHT Architectural Dimming 11