Chicago Electric 93188 Plumbing Product User Manual


 
Page 8SKU 93188 For technical questions, please call 1-800-444-3353
If you are using one extension cord for more than one tool, add the nameplate5. amperes
and use the sum to determine the required minimum cord size.
(See Figure C.)
If you are using an extension cord outdoors, make sure it is marked with the suffix “W-A” 6.
(“W” in Canada) to indicate it is acceptable for outdoor use.
Make sure your extension cord is properly wired and in good electrical condition. Al-7.
ways replace a damaged extension cord or have it repaired by a qualified electrician
before using it.
Protect your extension cords from sharp objects, excessive heat, and damp or wet 8.
areas.
RECOMMENDED MINIMUM WIRE GAUGE FOR EXTENSION CORDS*
(120 OR 240 VOLT)
NAMEPLATE
AMPERES
(at full load)
EXTENSION CORD LENGTH
25 Feet 50 Feet 75 Feet 100 Feet 150 Feet
0 – 2.0 18 18 18 18 16
2.1 – 3.4 18 18 18 16 14
3.5 – 5.0 18 18 16 14 12
5.1 – 7.0 18 16 14 12 12
7.1 – 12.0 18 14 12 10 -
12.1 – 16.0 14 12 10 - -
16.1 – 20.0 12 10 - - -
FIGURE C
* Based on limiting the line voltage drop to five volts at 150% of the rated amperes.