50YCS060 / 38WQS060 With GAH060
Performance capacities shown in thousands of Btuh.
WPD HEATING - EAT 70°F COOLING - EAT 80/67 °F
EWT °F GPM
PSI FT
CFM
HC KW HE LAT COP HWC TC SC KW HR EER HWC
7.5 1.6 3.7 1650
2000 Operation not recommended
20 11.3 3.2 7.4 1650 Operation not recommended
2000
15.0 5.1 11.8 1650 41.1 4.04 27.3 93.0 2.98 5.3
2000 41.5 3.99 27.9 89.2 3.05 4.5
7.5 1.6 3.6 1650 43.1 4.09 29.2 94.2 3.09 6.0 67.5 44.2 2.64 76.5 25.5 2.2
2000 43.8 4.05 30.0 90.3 3.17 5.0 69.1 47.2 2.73 78.5 25.3 1.8
30 11.3 3.1 7.1 1650 45.5 4.13 31.4 95.5 3.23 6.2 67.6 43.9 2.58 76.4 26.2 2.3
2000 46.1 4.09 32.2 91.4 3.30 5.3 68.8 46.7 2.68 77.9 25.7 1.9
15.0 4.9 11.4 1650 47.9 4.18 33.6 96.9 3.36 6.4 67.6 43.6 2.52 76.2 26.9 2.3
2000 48.5 4.13 34.4 92.4 3.44 5.5 68.4 46.1 2.63 77.4 26.0 2.0
7.5 1.5 3.5 1650 50.4 4.29 35.8 98.3 3.45 7.0 65.3 43.5 3.05 75.7 21.4 3.8
2000 51.3 4.25 36.8 93.7 3.54 6.0 66.8 46.5 3.15 77.6 21.2 3.5
40 11.3 3.0 6.9 1650 53.0 4.35 38.2 99.8 3.57 7.3 65.4 43.3 2.96 75.5 22.1 3.5
2000 53.3 4.28 38.7 94.7 3.65 6.2 66.5 46.0 3.07 77.0 21.7 3.4
15.0 4.8 11.1 1650 55.7 4.42 40.6 101.3 3.69 7.5 65.5 43.0 2.86 75.2 22.9 3.2
2000 55.3 4.32 40.6 95.6 3.75 6.5 66.3 45.5 2.99 76.5 22.1 3.2
7.5 1.5 3.4 1650 57.7 4.48 42.4 102.4 3.77 8.0 63.1 42.9 3.46 74.9 18.2 5.4
2000 58.7 4.44 43.5 97.2 3.87 7.0 64.6 45.8 3.58 76.8 18.1 5.2
50 11.3 2.9 6.7 1650 60.6 4.57 45.0 104.0 3.88 8.3 63.2 42.6 3.34 74.6 18.9 4.8
2000 60.4 4.48 45.2 98.0 3.96 7.2 64.3 45.3 3.47 76.1 18.6 4.8
15.0 4.6 10.7 1650 63.5 4.66 47.6 105.6 3.99 8.6 63.3 42.4 3.21 74.2 19.7 4.1
2000 62.2 4.51 46.8 98.8 4.04 7.5 64.1 44.8 3.36 75.5 19.1 4.4
7.5 1.4 3.3 1650 64.9 4.68 48.9 106.4 4.06 9.1 61.6 41.9 3.78 74.6 16.3 6.6
2000 66.1 4.64 50.3 100.6 4.17 7.9 63.1 45.4 3.90 76.4 16.2 6.5
60 11.3 2.8 6.5 1650 68.1 4.79 51.7 108.2 4.16 9.4 61.9 41.7 3.61 74.2 17.1 6.0
2000 68.5 4.67 52.6 101.7 4.30 8.2 63.2 45.0 3.74 75.9 16.9 6.1
15.0 4.5 10.4 1650 71.3 4.90 54.5 110.0 4.26 9.7 62.1 41.4 3.45 73.9 18.0 5.4
2000 71.0 4.71 54.9 102.9 4.42 8.5 63.2 44.6 3.58 75.4 17.7 5.6
7.5 1.4 3.2 1650 72.2 4.88 55.5 110.5 4.33 10.1 60.2 41.0 4.11 74.2 14.7 7.8
2000 73.5 4.83 57.0 104.0 4.45 8.9 61.7 45.0 4.23 76.1 14.6 7.9
70 11.3 2.7 6.3 1650 75.6 5.01 58.5 112.4 4.42 10.4 60.6 40.7 3.89 73.9 15.6 7.2
2000 76.6 4.87 60.0 105.5 4.61 9.2 62.0 44.7 4.02 75.7 15.4 7.3
15.0 4.3 10.0 1650 79.0 5.15 61.5 114.4 4.50 10.8 61.0 40.4 3.68 73.5 16.6 6.6
2000 79.7 4.90 63.0 106.9 4.77 9.5 62.4 44.3 3.80 75.4 16.4 6.8
7.5 1.3 3.1 1650 79.4 5.08 62.1 114.6 4.58 11.3 57.6 40.2 4.56 73.2 12.6 9.0
2000 80.9 5.03 63.7 107.5 4.71 9.7 59.0 44.2 4.70 75.0 12.5 9.2
80 11.3 2.6 6.1 1650 82.7 5.20 64.9 116.4 4.66 11.7 58.0 40.0 4.32 72.7 13.4 8.4
2000 83.8 5.05 66.6 108.8 4.86 10.1 59.3 43.8 4.46 74.5 13.3 8.6
15.0 4.2 9.7 1650 86.0 5.33 67.8 118.2 4.73 12.1 58.3 39.7 4.09 72.3 14.3 7.8
2000 86.7 5.07 69.4 110.1 5.01 10.5 59.7 43.5 4.22 74.1 14.1 8.0
7.5 1.3 3.0 1650 86.7 5.28 68.7 118.7 4.81 12.5 55.0 39.5 5.02 72.1 11.0 10.2
2000 88.3 5.23 70.5 110.9 4.95 10.5 56.3 43.4 5.17 73.9 10.9 10.6
90 11.3 2.5 5.9 1650 89.8 5.39 71.4 120.4 4.88 13.0 55.3 39.2 4.76 71.5 11.6 9.6
2000 91.0 5.24 73.1 112.1 5.09 11.0 56.6 43.0 4.90 73.3 11.5 9.9
15.0 4.1 9.4 1650 92.9 5.51 74.1 122.1 4.94 13.5 55.6 39.0 4.49 71.0 12.4 9.0
2000 93.7 5.25 75.8 113.4 5.23 11.5 56.9 42.7 4.64 72.8 12.3 9.2
7.5 1.2 2.9 1650 53.3 39.1 5.56 72.3 9.6 11.5
2000 54.6 42.9 5.72 74.1 9.5 11.9
100 11.3 2.4 5.6 1650 53.7 38.8 5.27 71.6 10.2 10.8
2000 54.9 42.6 5.43 73.5 10.1 11.2
15.0 3.9 9.0 1650 54.0 38.5 4.98 71.0 10.8 10.2
2000 Operation not recommended 55.3 42.2 5.14 72.8 10.7 10.4
7.5 1.2 2.8 1650 51.7 38.6 6.10 72.5 8.5 12.8
2000 52.9 42.5 6.28 74.4 8.4 13.3
110 11.3 2.4 5.4 1650 52.0 38.4 5.78 71.8 9.0 12.1
2000 53.3 42.1 5.96 73.6 8.9 12.5
15.0 3.8 8.7 1650 52.4 38.1 5.46 71.0 9.6 11.4
2000 53.6 41.8 5.64 72.8 9.5 11.6
Rev: 12/12/03 BInterpolation is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based on 15% antifreeze solution.
See performance correction tables for operating conditions other than those listed above.
Table does not reflect fan or pump power ISO corrections.