29
50YCS030 / 38WQS030 With GAH030
Performance capacities shown in thousands of Btuh.
WPD HEATING - EAT 70°F COOLING - EAT 80/67 °F
EWT °F GPM
PSI FT
CFM
HC KW HE LAT COP HWC TC SC KW HR EER HWC
3.7 0.6 1.5 800
1000 Operation not recommended
20 5.5 1.4 3.3 800 Operation not recommended
1000
7.5 2.7 6.2 800 18.4 1.92 11.9 91.3 2.82 2.6
1000 18.6 1.88 12.2 87.2 2.91 2.2
3.7 0.6 1.4 800 20.6 1.97 13.9 93.8 3.06 2.9 34.5 22.6 1.09 38.2 31.6 1.1
1000 20.7 1.92 14.1 89.1 3.15 2.5 36.0 25.2 1.04 39.5 34.4 0.9
30 5.5 1.4 3.2 800 21.5 1.96 14.8 94.9 3.20 3.0 34.6 22.4 1.07 38.3 32.4 1.1
1000 21.6 1.92 15.1 90.0 3.30 2.6 36.0 24.7 1.09 39.7 33.1 1.0
7.5 2.6 6.0 800 22.4 1.96 15.7 95.9 3.35 3.2 34.8 22.2 1.05 38.4 33.2 1.2
1000 22.6 1.92 16.1 90.9 3.45 2.7 36.1 24.1 1.14 40.0 31.8 1.0
3.7 0.6 1.4 800 24.0 2.03 17.1 97.8 3.48 3.4 33.5 22.3 1.31 37.9 25.5 1.9
1000 24.1 1.98 17.4 92.4 3.58 3.0 34.9 25.0 1.25 39.2 27.8 1.8
40 5.5 1.3 3.1 800 24.9 2.04 18.0 98.9 3.58 3.6 33.6 22.2 1.26 37.9 26.7 1.8
1000 24.9 1.98 18.2 93.1 3.68 3.1 34.9 24.4 1.28 39.3 27.3 1.7
7.5 2.5 5.8 800 25.8 2.06 18.8 99.9 3.68 3.7 33.7 22.1 1.20 37.8 28.0 1.6
1000 25.7 1.99 18.9 93.8 3.78 3.2 35.0 23.9 1.31 39.5 26.8 1.6
3.7 0.6 1.3 800 27.5 2.08 20.4 101.8 3.87 4.0 32.4 22.1 1.53 37.7 21.2 2.7
1000 27.6 2.03 20.7 95.6 3.99 3.4 33.8 24.7 1.47 38.8 23.1 2.6
50 5.5 1.3 3.0 800 28.4 2.12 21.2 102.8 3.93 4.1 32.6 22.0 1.45 37.5 22.5 2.4
1000 28.2 2.05 21.2 96.1 4.04 3.6 33.9 24.2 1.47 38.9 23.0 2.4
7.5 2.4 5.6 800 29.3 2.16 21.9 103.9 3.98 4.2 32.7 21.9 1.36 37.3 24.0 2.1
1000 28.8 2.06 21.8 96.6 4.09 3.7 33.9 23.8 1.48 39.0 23.0 2.2
3.7 0.6 1.3 800 31.0 2.17 23.6 105.8 4.19 4.5 31.2 21.4 1.66 36.9 18.8 3.3
1000 31.1 2.09 24.0 98.8 4.37 3.9 32.7 23.8 1.67 38.3 19.6 3.3
60 5.5 1.3 2.9 800 31.8 2.21 24.3 106.8 4.22 4.6 31.2 21.1 1.59 36.7 19.7 3.0
1000 32.0 2.11 24.8 99.6 4.45 4.1 32.7 23.5 1.62 38.3 20.2 3.0
7.5 2.4 5.4 800 32.7 2.25 25.0 107.9 4.25 4.8 31.2 20.8 1.52 36.4 20.6 2.7
1000 32.9 2.13 25.6 100.4 4.52 4.2 32.8 23.1 1.58 38.2 20.7 2.8
3.7 0.5 1.3 800 34.4 2.25 26.8 109.9 4.48 5.0 30.0 20.7 1.79 36.2 16.8 3.9
1000 34.6 2.14 27.3 102.0 4.73 4.4 31.5 23.0 1.87 37.9 16.9 3.9
70 5.5 1.2 2.8 800 35.3 2.30 27.4 110.8 4.50 5.2 29.9 20.2 1.73 35.8 17.3 3.6
1000 35.8 2.17 28.4 103.1 4.83 4.5 31.6 22.8 1.78 37.7 17.8 3.7
7.5 2.3 5.3 800 36.1 2.35 28.1 111.8 4.51 5.3 29.7 19.7 1.67 35.5 17.8 3.3
1000 37.0 2.20 29.5 104.2 4.92 4.7 31.7 22.5 1.69 37.5 18.8 3.4
3.7 0.5 1.2 800 37.9 2.31 30.0 113.9 4.81 5.6 29.0 20.7 2.00 35.9 14.5 4.5
1000 38.0 2.20 30.5 105.2 5.08 4.8 30.5 23.0 2.08 37.6 14.7 4.6
80 5.5 1.2 2.7 800 38.6 2.37 30.5 114.7 4.77 5.8 28.9 20.2 1.93 35.5 15.0 4.2
1000 39.1 2.24 31.5 106.2 5.12 5.0 30.6 22.7 1.98 37.3 15.4 4.3
7.5 2.2 5.1 800 39.3 2.44 31.0 115.5 4.73 6.0 28.7 19.7 1.87 35.1 15.4 3.9
1000 40.2 2.28 32.4 107.2 5.17 5.2 30.6 22.5 1.89 37.1 16.3 4.0
3.7 0.5 1.2 800 41.4 2.37 33.3 117.9 5.12 6.2 28.0 20.7 2.20 35.5 12.7 5.1
1000 41.5 2.25 33.8 108.4 5.41 5.2 29.4 23.0 2.30 37.3 12.8 5.3
90 5.5 1.1 2.6 800 41.9 2.44 33.6 118.5 5.03 6.4 27.9 20.2 2.13 35.2 13.1 4.8
1000 42.5 2.31 34.6 109.3 5.40 5.5 29.5 22.7 2.19 37.0 13.5 4.9
7.5 2.1 4.9 800 42.5 2.52 33.9 119.2 4.94 6.7 27.7 19.7 2.06 34.8 13.5 4.5
1000 43.5 2.36 35.4 110.3 5.40 5.7 29.6 22.5 2.08 36.7 14.2 4.6
3.7 0.5 1.1 800 26.4 19.6 2.39 34.6 11.0 5.8
1000 27.7 21.8 2.49 36.2 11.1 6.0
100 5.5 1.1 2.5 800 26.3 19.2 2.32 34.2 11.4 5.4
1000 27.8 21.6 2.38 35.9 11.7 5.6
7.5 2.0 4.7 800 26.2 18.7 2.24 33.8 11.7 5.1
1000 Operation not recommended 27.9 21.3 2.26 35.6 12.3 5.2
3.7 0.5 1.1 800 24.8 18.6 2.58 33.6 9.6 6.4
1000 26.0 20.6 2.69 35.2 9.7 6.7
110 5.5 1.1 2.4 800 24.7 18.1 2.50 33.2 9.9 6.0
1000 26.1 20.4 2.57 34.9 10.2 6.2
7.5 2.0 4.5 800 24.6 17.7 2.42 32.8 10.2 5.7
1000 26.2 20.2 2.44 34.5 10.7 5.8
Rev: 12/12/03 B
Operation below 40°F EWT is based on 15% antifreeze solution.
See performance correction tables for operating conditions other than those listed above.
Table does not reflect fan or pump power ISO corrections.
Interpolation is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.