Carrier GT-G Heat Pump User Manual


 
Carrier
Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05
34
Physical Data
GT-S (38WQS) Physical Data
GT-GS (50YCS) Physical Data
GT-PX (50YDS) Physical Data
Model 026 038 049 064
Compressor [1 Each) Copeland UltraTech Two-Stage Scroll
Factory Charge R410A (oz) [kg] 90 [2.55] 104 [2.95] 126 [3.57] 168 [4.76]
Water Connection Size
IPT (in) 1 1 1 1
HWG Connection Size
IPT (in) 1 1 1 1
Line Set Connection Size
Suction Line Sweat Connection (in.) 3/4 7/8 7/8 1-1/8
Liquid Line Sweat Connection (in.) 3/8 3/8 3/8 1/2
Weight - Operating, (lbs) [kg] 203 [92] 221 [100] 250 [113] 265 [120]
Weight - Packaged, (lbs) [kg] 218 [99] 236 [107] 265 [120] 280 [127]
Model 018 024 030 036 042 048 060
Compressor [1 Each) Scroll
Factory Charge R410A (oz) [kg] 90 [2.55] 104 [2.95] 108 [3.06] 117 [3.32] 122 [3.46] 130 [3.69] 136 [3.86]
Water Connection Size
IPT (in) 1 1 1 1 1 1 1
HWG Connection Size
IPT (in) 1 1 1 1 1 1 1
Line Set Connection Size
Suction Line Sweat Connection (in.) 3/4 7/8 7/8 7/8 7/8 7/8 1-1/8
Liquid Line Sweat Connection (in.) 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Weight - Operating, (lbs) [kg] 165 [75] 203 [92] 205 [93] 217 [98] 221 [100] 229 [104] 235 [107]
Weight - Packaged, (lbs) [kg] 180 [82] 218 [99] 220 [100] 232 [105] 236 [107] 244 [111] 250 [113]
Model 018 024 030 036 042 048 060
Compressor [1 Each) Rotary Scroll
Factory Charge R410A (oz) [kg] 70 [1.98] 74 [2.10] 86 [2.52] 101 [2.86] 122 [3.46] 130 [3.69] 136 [3.86]
Water Connection Size
EPT (in) 1-1/4
Line Set Connection Size
Suction Line Sweat Connection (in.) 3/4 3/4 7/8 7/8 7/8 7/8 1-1/8
Liquid Line Sweat Connection (in.) 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Weight - Operating, (lbs) [kg] 165 [75] 203 [92] 205 [93] 217 [98] 221 [100] 229 [104] 235 [107]
Weight - Packaged, (lbs) [kg] 180 [82] 218 [99] 220 [100] 232 [105] 236 [107] 244 [111] 250 [113]
All units have spring compressor mountings, TXV expansion devices, and 1/2” [12.2mm] & 3/4” [19.1mm] electrical knockouts.
All units have spring compressor mountings, TXV expansion devices, and 1/2” [12.2mm] & 3/4” [19.1mm] electrical knockouts.
All units have spring compressor mountings, TXV expansion devices, weather resistant cabinet, and 1/2” [12.2mm] & 3/4”
[19.1mm] electrical knockouts. Hot Water Generator with factory installed hot gas service ports.