Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05
32
50YCS048 / 38WQS048 With GAH048
Performance capacities shown in thousands of Btuh.
WPD HEATING - EAT 70°F COOLING - EAT 80/67 °F
EWT °F GPM
PSI FT
CFM
HC KW HE LAT COP HWC TC SC KW HR EER HWC
6.0 2.6 5.9 1300
1600 Operation not recommended
20 9.0 4.9 11.2 1300 Operation not recommended
1600
12.0 7.6 17.6 1300 30.1 3.01 19.8 91.4 2.93 4.2
1600 31.4 2.95 21.3 88.2 3.12 3.6
6.0 2.5 5.8 1300 34.2 2.99 24.0 94.3 3.35 4.8 54.9 35.5 1.91 61.4 28.7 1.7
1600 36.7 2.98 26.5 91.2 3.61 4.0 56.7 38.9 2.00 63.5 28.3 1.4
30 9.0 4.7 10.9 1300 34.8 3.04 24.4 94.8 3.35 5.0 54.9 35.7 1.84 61.1 29.9 1.7
1600 36.8 3.01 26.5 91.3 3.58 4.2 56.5 38.7 1.93 63.1 29.4 1.5
12.0 7.4 17.1 1300 35.4 3.10 24.8 95.2 3.35 5.1 54.8 35.9 1.76 60.9 31.1 1.8
1600 36.9 3.04 26.5 91.4 3.56 4.4 56.4 38.5 1.85 62.7 30.5 1.6
6.0 2.4 5.6 1300 37.9 3.07 27.4 97.0 3.61 5.6 53.4 34.9 2.19 60.9 24.4 3.0
1600 40.7 3.07 30.2 93.6 3.89 4.8 55.1 38.2 2.30 63.0 24.0 2.8
40 9.0 4.6 10.6 1300 39.1 3.13 28.4 97.8 3.66 5.8 53.3 35.1 2.11 60.5 25.3 2.8
1600 41.3 3.09 30.7 93.9 3.92 5.0 54.9 38.0 2.21 62.4 24.9 2.6
12.0 7.2 16.6 1300 40.3 3.19 29.4 98.7 3.71 6.0 53.2 35.2 2.03 60.1 26.3 2.6
1600 41.9 3.11 31.3 94.2 3.95 5.2 54.7 37.8 2.12 61.9 25.8 2.5
6.0 2.3 5.4 1300 41.6 3.16 30.8 99.6 3.86 6.4 51.9 34.2 2.47 60.3 21.0 4.3
1600 44.7 3.15 33.9 95.9 4.15 5.6 53.6 37.5 2.59 62.4 20.7 4.1
50 9.0 4.4 10.2 1300 43.4 3.21 32.4 100.9 3.95 6.7 51.7 34.4 2.38 59.9 21.8 3.8
1600 45.8 3.16 35.0 96.5 4.24 5.8 53.3 37.3 2.49 61.8 21.4 3.8
12.0 7.0 16.1 1300 45.2 3.27 34.0 102.2 4.05 6.9 51.6 34.6 2.29 59.4 22.6 3.3
1600 46.8 3.17 36.0 97.1 4.33 6.0 53.0 37.1 2.40 61.2 22.1 3.5
6.0 2.3 5.2 1300 46.9 3.26 35.8 103.4 4.21 7.3 50.1 33.6 2.71 59.4 18.5 5.3
1600 48.7 3.24 37.6 98.2 4.40 6.3 52.7 37.2 2.83 62.4 18.6 5.2
60 9.0 4.3 9.9 1300 48.5 3.31 37.2 104.5 4.29 7.5 50.1 33.6 2.62 59.1 19.2 4.8
1600 50.3 3.25 39.2 99.1 4.53 6.6 52.4 37.0 2.73 61.7 19.2 4.8
12.0 6.7 15.6 1300 50.1 3.36 38.6 105.7 4.37 7.7 50.1 33.6 2.52 58.8 19.9 4.3
1600 52.0 3.27 40.8 100.1 4.66 6.8 52.0 36.9 2.62 60.9 19.8 4.5
6.0 2.2 5.1 1300 52.2 3.36 40.7 107.2 4.55 8.1 48.4 32.9 2.96 58.5 16.4 6.3
1600 52.6 3.32 41.3 100.5 4.64 7.1 51.9 36.9 3.07 62.4 16.9 6.3
70 9.0 4.1 9.6 1300 53.6 3.40 42.0 108.1 4.62 8.4 48.5 32.8 2.86 58.3 17.0 5.8
1600 54.9 3.35 43.5 101.8 4.81 7.3 51.4 36.8 2.96 61.5 17.4 5.9
12.0 6.5 15.1 1300 54.9 3.44 43.2 109.1 4.68 8.6 48.7 32.7 2.76 58.1 17.7 5.3
1600 57.1 3.37 45.6 103.0 4.97 7.6 50.9 36.6 2.85 60.6 17.9 5.5
6.0 2.1 4.9 1300 56.1 3.45 44.3 110.0 4.77 9.0 46.6 32.1 3.26 57.7 14.3 7.2
1600 56.6 3.41 45.0 102.8 4.87 7.8 50.0 36.0 3.39 61.5 14.7 7.4
80 9.0 4.0 9.3 1300 57.2 3.48 45.4 110.8 4.82 9.4 46.7 32.0 3.15 57.5 14.8 6.7
1600 58.6 3.43 47.0 103.9 5.01 8.1 49.5 35.8 3.26 60.6 15.2 6.9
12.0 6.3 14.6 1300 58.4 3.52 46.4 111.6 4.86 9.7 46.9 31.9 3.04 57.2 15.4 6.3
1600 60.7 3.44 48.9 105.1 5.16 8.4 49.0 35.7 3.14 59.7 15.6 6.4
6.0 2.0 4.7 1300 60.1 3.53 48.0 112.8 4.98 10.0 44.8 31.3 3.57 57.0 12.6 8.2
1600 60.6 3.49 48.7 105.1 5.08 8.4 48.0 35.0 3.71 60.7 13.0 8.5
90 9.0 3.9 8.9 1300 60.9 3.56 48.8 113.4 5.01 10.4 44.9 31.2 3.45 56.7 13.0 7.7
1600 62.4 3.51 50.4 106.1 5.21 8.8 47.6 34.9 3.57 59.7 13.3 8.0
12.0 6.1 14.0 1300 61.8 3.60 49.5 114.0 5.04 10.8 45.1 31.1 3.33 56.4 13.6 7.2
1600 64.2 3.52 52.2 107.2 5.35 9.2 47.1 34.8 3.43 58.8 13.7 7.4
6.0 2.0 4.5 1300 43.1 30.9 3.99 56.7 10.8 9.3
1600 46.3 34.6 4.14 60.4 11.2 9.6
100 9.0 3.7 8.6 1300 43.3 30.8 3.85 56.4 11.2 8.7
1600 45.8 34.5 3.99 59.4 11.5 9.0
12.0 5.9 13.5 1300 43.4 30.7 3.72 56.1 11.7 8.2
1600 Operation not recommended 45.4 34.4 3.84 58.4 11.8 8.4
6.0 1.9 4.4 1300 41.5 30.6 4.41 56.5 9.4 10.3
1600 44.5 34.2 4.58 60.1 9.7 10.7
110 9.0 3.6 8.3 1300 41.6 30.5 4.26 56.1 9.8 9.7
1600 44.1 34.1 4.41 59.1 10.0 10.0
12.0 5.6 13.0 1300 41.7 30.4 4.11 55.8 10.2 9.2
1600 43.6 34.0 4.24 58.1 10.3 9.4
Rev: 12/12/03 BInterpolation is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based on 15% antifreeze solution.
See performance correction tables for operating conditions other than those listed above.
Table does not reflect fan or pump power ISO corrections.