CONTROLS
Operating sequence
Cooling When the system thermostat calls for cooling, 24 V is
supplied to the “Y” and “G” terminals of the thermostat. This
completes the circuit to the contactor coil (C) and indoor fan
board. The normally open contacts of C close and complete the
circuit to compressor motor (COMP) and to outdoor (condenser)
fan motor (OFM). Both motors start instantly. The IFM starts
according to the selection pin set--up on the Easy Select Board.
On the loss of the thermostat call for cooling, 24 V is removed
from both the “Y” and “G” terminals (provided the fan switch is in
the “AUTO” position) de--energizing the compressor contactor and
opening the contacts supplying power to compressor/OFM. After a
preselected delay, the I FM shuts of f. If the thermostat fan selector
switch is in the “ON” position, the IFM will run continuously at
speed selected on Easy Select Board
Heating If accessory electric heaters are installed, on a call for
heat, circuit R--W is made through the thermostat contacts. Circuit
R--G is made which energizes the IFM. If the heaters are staged,
then the thermostat closes a second set of contacts (W2) when
second stage is required. When thermostat is satisfied, contacts
open, deenergizing the heater relay. After a preselected delay , the
IFM shuts of f. If the thermostat fan selector switch is in the “ON”
position, the IFM will run continuously at speed selected on Easy
Select Board.
NOTE: On units with a Time Guard
®
II device: Once the
compressor has started and then stopped, it cannot be restarted
again until 5 minutes have elapsed.
The indoor blower operation with a call for fan operation (G) in
cooling mode will perform by the on/off delay profile selected at
start up on the Easy Select Board.
50XP