PERFORMANCE DATA (CONT)
*At75°F(24°C)entering dry bulb---TennesseeValleyAuthority (TVA) rating conditions;all others at 80°F(27°C) dry bulb.
LEGEND
BF—BypassFactor
edb— Entering Dry---Bulb
Ewb— Entering Wet---Bulb
kW— Total Unit PowerInput
SHC— Sensible HeatCa pacity (1000 Btuh)
TC — Total Capacity (1000 Btuh) (n et)
rh—Relative Humidity
COOLING NOTES:
1.Ratingsarenet; they accountfor theeffectsof the evaporator---fan motorpower andheat.
2. Direct interpolationispermissible. Donot extrapolate.
3.The followingformulasmay be used:
Sensible capacity
(Btuh)
1.10 x cfm
t
ldb =
t
edb
---
Wet---bulb temperature corresponding to enthalpy
air l eaving evaporator coil (
h
lwb)
t
lwb =
total capacity (Btuh)
4.5 x cfm
h
lwb =
h
ewb ---
Where:
h
ewb= Enthalpy of air entering evaporator coil
4. The SHC isbased on 805F (26.6_C)edb temperature of air enteringevaporator coil. Below80_F (26.6_C) edb, subtract (corr factor x cfm) from SHC.
Above 80_F (26.6_C) edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10x (1 + BF) x (edb+ 80).
5. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil andthe heat required to defrost it.
50XP