POINT NAME EDITABLE RANGE DEFAULT NOTES
Configuration
Set Points
User/Admin
Password level
access
Occupied Heating X 40 - 90 F 72 F
Defines the Occupied
Heating Set Point
Occupied Cooling X 55 - 99 F 76 F
Defines the Occupied
Cooling Set Point
Unoccupied Heating X 40 - 90 F 55 F
Defines the Unoccupied
Heating Set Point
Unoccupied Cooling X 55 - 99 F 90 F
Defines the Unoccupied
Cooling Set Point
Effective Heating
Set Point
X0 - 10 F
Takes into effect bias (maximum
allowable set point deviation)
Effective Cooling
Set Point
X0 - 10 F
Takes into effect bias (maximum
allowable set point deviation)
Optimal Start
Uses historical data to calculate
ramp up time so as to be at set point
at occupied/unoccupied time
Occupied RH
Set Point
X 0 - 100% 65%
Defines the control set point used
during occupied periods (Viewable
only if Humidity Sensor = Installed/
Determines when to start
Dehumidification when occupied)
Unoccupied RH
Set Point
X 0 - 100% 90%
Defines the control set point used
during unoccupied periods
(Viewable only if Humidity Sensor =
Installed/Determines when to start
Dehumidification when unoccupied)
DCV CTRL Start
Set Point
X 0 - 9999 ppm 500 ppm
Defines the control set point used to
start increasing ventilation during
occupied periods (Viewable only if
Ventilation DMP Type = DCV)
DCV Max CTRL
Set Point
X 0 - 9999 ppm 1050 ppm
Defines the control set point
used to define where the ventilation
will reach its maximum limit during
occupied periods (Viewable only if
Ventilation DMP Type = DCV/Used
to determine DCV ending control
point)
Configuration
Schedule
Weekly Schedule
User/Admin
Password level
access
Start Time X 00:00 - 23:59 06:00
Defines the start time for an
occupied period
End Time X 00:00 - 24:00 18:00
Defines the ending time of an
occupied period
Mon X No/Yes Yes
Determines if this day is included
in this schedule
Tu e X N o/Ye s Yes
Determines if this day is included
in this schedule
Wed X No/Yes Yes
Determines if this day is included
in this schedule
Thur X No/Yes Yes
Determines if this day is included
in this schedule
Fri X No/Yes Yes
Determines if this day is included
in this schedule
Sat X No/Yes No
Determines if this day is included
in this schedule
Sun X No/Yes No
Determines if this day is included
in this schedule
Configuration
Schedule
Exception
Schedules 1 - 12
User/Admin
Password level
access
Start Month X 0 - 12 0
Defines the start month of this
hoilday schedule
Start Day X 0 - 31 0
Defines the start day of this holiday
schedule
Start Time X 00:00 - 23:59 0:00
Determines the start time for this
schedule
End Month X 0 - 12 0
Defines the month to end this
hoilday schedule
End Day X 0 - 31 0
Defines the day to end this holiday
schedule
End Time X 00:00 - 24:00 0:00
Determines the time to end this
schedule
BAS Building Automation System
DCV Demand Controlled Ventilation
ECM Electronically Commutated Motor
IAQ Indoor Air Quality
OAT Outdoor Air Temperature
RH Relative Humidity
SAT Supply Air Temperature
SPT Space Temperature
TPI Third Party Integration