Carrier 50PCH Heat Pump User Manual


 
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500094-01 Printed in U.S.A. Form 50PC-3SI CL-2 5-11A 3-11 Replaces: 50PC-2SI
Copyright 2011 Carrier Corporation
-
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
HEATING CYCLE ANALYSIS
COOLING CYCLE ANALYSIS
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (GPM) x TEMP. DIFF. (DEG. F) x FLUID FACTOR* =
(Btu/hr)
SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE
=
(DEG F)
SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE
=
(DEG F)
*Use 500 for water, 485 for antifreeze.
a50-8445
SUCTION
COMPRESSOR
DISCHARGE
COAX
EXPANSION
VALVE
F
F
AIR
COIL
F
PSI
WATER OUT
WATER IN
F
PSI
LOOK UP PRESSURE DROP IN TABLE 26
TO DETERMINE FLOW RATE
F
LIQUID LINE
PSI
F
SAT
a50-8446
SUCTION
COMPRESSOR
DISCHARGE
COAX
EXP ANSION
VA LV E
°F
°F
AI R
COI L
°F
PSI
WA TER OUT
WA TER IN
°F
PSI
LOOK UP PRESSURE DROP IN T ABLE 26
TO DETERMINE FLOW RA TE
°F
LIQUID LIN E
PSI
°F
SA T
97B0038N05