19
Table 3 — 50PCH,PCV Unit Electrical Data
LEGEND *Units using 460-v and ECM (electronically commutated motor), modulating
HWR (hot water reheat), and/or internal secondary pump will require a neutral
wire from the supply side in order to feed accessory with 265-v.
NOTES:
1. HACR circuit breaker in U.S.A. only.
2. All fuses
3. Class RK-5.
50PCH,PCV
UNIT
VOLTAGE
CODE
RATED
VOLTAGE
V-Ph-Hz*
VOLTAGE
MIN/MAX
COMPRESSOR STANDARD UNITS UNITS WITH HIGH-STATIC BLOWER
QTY RLA LRA
Fan Motor
FLA
Total Unit
FLA
Min Circuit
AMP
Max Fuse/
HACR
Fan Motor
FLA
Total Unit
FLA
Min Circuit
AMP
Max Fuse/
HACR
006
3 208/230-1-60 197/254 1 3.3 17.7 0.40 3.7 4.5 15
—— — —
4 265-1-60 239/292 1 2.9 13.5 0.40 3.3 4.0 15 —— — —
009
3 208/230-1-60 197/254 1 5.6 22.2 0.80 6.4 7.8 15
—— — —
4 265-1-60 239/292 1 3.8 18.8 0.70 4.5 5.5 15 —— — —
012
3 208/230-1-60 197/254 1 5.1 32.5 0.80 5.9 7.2 15
—— — —
4 265-1-60 239/292 1 4.0 31.5 0.70 4.7 5.7 15 —— — —
015
3 208/230-1-60 197/254 1 6.0 29.0 1.00 7.0 8.5 15 1.00 7.0 8.5 15
4 265-1-60 239/292 1 5.4 28.0 0.86 6.3 7.6 15 0.86 6.3 7.6 15
018
3 208/230-1-60 197/254 1 7.2 33.0 1.00 8.2 10.0 15 1.50 8.7 10.5 15
4 265-1-60 239/292 1 5.9 28.0 0.86 6.8 8.2 15 1.30 7.2 8.7 15
024
3 208/230-1-60 197/254 1 12.8 58.3 1.50 14.3 17.5 30 3.00 15.8 19.0 30
4 265-1-60 239/292 1 9.6 54.0 1.30 10.9 13.3 20 2.70 12.3 14.7 20
030
3 208/230-1-60 197/254 1 14.1 73.0 3.00 17.1 20.6 30 3.00 17.1 20.6 30
4 265-1-60 239/292 1 11.2 60.0 2.70 13.9 16.7 25 2.70 13.9 16.7 25
5 208/230-3-60 197/254 1 8.9 58.0 3.00 11.9 14.1 20 3.00 11.9 14.1 20
6 460-3-60 414/506 1 4.2 28.0 1.70 5.9 7.0 15 1.70 5.9 7.0 15
036
3 208/230-1-60 197/254 1 16.7 79.0 1.80 18.5 22.7 35 3.00 19.7 23.9 40
4 265-1-60 239/292 1 13.5 72.0 2.00 15.5 18.9 30 2.70 16.2 19.6 30
5 208/230-3-60 197/254 1 10.4 73.0 1.80 12.2 14.8 25 3.00 13.4 16.0 25
6 460-3-60 414/506 1 5.8 38.0 1.24 7.0 8.5 15 1.70 7.5 9.0 15
042
3 208/230-1-60 197/254 1 17.9 112.0 3.00 20.9 25.4 40 3.00 20.9 25.4 40
5 208/230-3-60 197/254 1 13.5 88.0 3.00 16.5 19.9 30 3.00 16.5 19.9 30
6 460-3-60 414/506 1 6.0 44.0 1.70 7.7 9.2 15 1.70 7.7 9.2 15
1 575-3-60 518/633 1 4.9 34.0 1.40 6.3 7.5 15 1.40 6.3 7.5 15
048
3 208/230-1-60 197/254 1 21.8 117.0 3.40 25.2 30.7 50 4.90 26.7 32.2 50
5 208/230-3-60 197/254 1 13.7 83.1 3.40 17.1 20.5 30 4.90 18.6 22.0 35
6 460-3-60 414/506 1 6.2 41.0 1.80 8.0 9.6 15 2.50 8.7 10.3 15
1 575-3-60 518/633 1 4.8 33.0 1.40 6.2 7.4 15 1.90 6.7 7.9 15
060
3 208/230-1-60 197/254 1 26.3 134.0 4.90 31.2 37.8 60 5.80 32.1 38.7 60
5 208/230-3-60 197/254 1 15.6 110.0 4.90 20.5 24.4 40 5.80 21.4 25.3 40
6 460-3-60 414/506 1 7.8 52.0 2.50 10.3 12.3 20 2.60 10.4 12.4 20
1 575-3-60 518/633 1 5.8 38.9 1.90 7.7 9.2 15 2.30 8.1 9.6 15
FLA — Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA — Locked Rotor Amps
RLA — Rated Load Amps
Fig. 21 — Typical Single-Phase Line Voltage Power Connection
a50-8162