Carrier 50CR Heat Pump User Manual


 
13
228 =1v
229 =2v
227 =2v
LEGEND
FLA Full Load Amps
LRA Locked Rotor Amps
MCA -- Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps
NO TES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NE C
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. The CGA (Canadian Gas
Association) units may be fuse or circuit break er.
2. Minimum wire size is based on 60 C copper wire. I f other than
60 C wire is used, or if length exceeds wire length in table,
determine siz efrom NEC..
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percentage of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 230-3-60.
AB = 228 v
BC = 231 v
AC = 227 v
228 + 231 + 227
Average Voltage =
3
686
=
3
= 229
Determine maximum deviation from average voltage.
(AB) 229 -
(BC) 231 -
(AC) 229 -
Maximum deviation is 2 v.
Determine percent of voltage imbalance.
2
% Voltage Imbalance = 100 x
229
= 0.8%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
®
*
Heater capacity (kW) based on heater voltage of 208v & 240v.
If power distibution voltage to unit varies from rated heater
volta
g
e, heater kW will var
y
accordin
g
l
y
.
C03014
Fig. 13 -- Electrical Data Legend
LEGEND
Field Control-Voltage
Wiring
D
C
B
A
User Interface
D
C
B
A
Infinity Control Board
OAT
RYOWCHUM
C
Humidifier
(Optional)
24vac
Outdoor Air Thermisto
r
(if used)
A05302
Fig. 14 -- Control Voltage Wiring Connections
50CR