Carrier 48EJ Gas Heater User Manual


 
UNIT
WEIGHT A B C
lb kg in. mm in. mm in. mm
48EJ,EK,EW,EYD024 4176 1894
87.68 2227
72.4 1839 42.4 1072
48EJ,EWE024 4256 1930 73.3 1862 42.7 1085
48EJ,EK,EW,EYD028
4262 1933 69.6 1768 44.0 111848EJ,EK,EW,EYD030
48EJ,EK,EW,EYD034
48EJ,EWE028
4342 1969 70.1 1781 44.3 112548EJ,EWE030
48EJ,EWE034
48EJ,EK,EW,EYD038 4442 2015
150 3810
92.7 2355 46.9 1191
48EJ,EWE038 4602 2087 94.1 2390 47.2 1199
48EJ,EK,EW,EYD044 4668 2117 89.3 2268 46.9 1191
48EJ,EWE044 4828 2190 90.8 2306 47.2 1199
48EJ,EK,EW,EYD048 4955 2248 87.7 2228 46.5 1181
48EJ,EWE048 5115 2320 89.2 2266 46.8 1189
NOTICE TO RIGGERS:
ALL PANELS MUST BE IN PLACE
WHEN RIGGING.
NOTE: Rig with four cables and spread with two
92 in. (2337 mm) spreader bars. Maintain a dis-
tance of 74 in. (1880 mm) from top of unit to
eyehook.
NOTE:
Add 32 lb (14.5 kg) for domestic crating.
Add 312 lb (142 kg) for export crating (024-034 units).
Add 346 lb (157 kg) for export crating (038-048 units).
Add 250 lb (113 kg) for power exhaust.
Add 220 lb (100 kg) for copper condenser coil (024-034 units).
Add 285 lb (129 kg) for copper condenser coil (038,044 units).
Add 380 lb (172 kg) for copper condenser coil (048 unit).
Fig. 7 Rigging Label
9