VFD — Variable Frequency Drive
NOTES:
1. Weights include economizer (STD).
2. Center of gravity.
3. Do not locate adjacent units with flue dis-
charge facingeconomizerinlet. Minimumclear-
ances to be:
Adjacent Units: 15Ј-0Љ
Top of Units: No overhang
Condenser Coil: 4Ј-0Љ
Economizer Side: 6Ј-0Љ
Gas Heat Side: 4Ј-0Љ
Filter Access Side: 10Ј-0Љ (For Removal of
Evaporator Coil)
4. For smaller service and operational clear-
ances, contact Carrier Application Engineer-
ing department.
5. Bottom ducts designed to be attached to ac-
cessory roof curb. If unit is mounted on dun-
nage, it is recommended the ducts be
supported by cross braces as done on ac-
cessory roof curb.
6. Dimensions are in inches.
UNIT
SIZE
OPERATING
WEIGHT
A B CORNER WEIGHT (lb)
lb ft-in. ft-in. 1 2 3 4
48EJ,EKD024 4176 6- 0
3
⁄
8
3-6
3
⁄
8
879 954 1220 1124
48EJE024 4256 6- 1
5
⁄
16
3-6
11
⁄
16
917 973 1218 1148
48EJ,EKD028 4262 5- 9
5
⁄
8
3-8 899 899 1232 1232
48EJE028 4342 5-10
1
⁄
8
3-8
5
⁄
16
929 916 1240 1257
48EJ,EKD030 4262 5- 9
5
⁄
8
3-8 899 899 1232 1232
48EJE030 4342 5-10
1
⁄
8
3-8
5
⁄
16
929 916 1240 1257
48EJ,EKD034 4262 5- 9
5
⁄
8
3-8 899 899 1232 1232
48EJE034 4342 5-10
1
⁄
8
3-8
5
⁄
16
929 916 1240 1257
Fig. 3 — Base Unit Dimensions, 48EJ,EK024-034
5