Carrier 38HDL018-060 Air Conditioner User Manual


 
SUBCOOLING METHOD (COOLING, TXV) — To check
and adjust charge during cooling season, use Tables 6A and
6B and the following procedure:
1. Operate unit a minimum of 15 minutes before checking
charge.
2. Measure liquid line temperature near liquid line service
valve, and measure liquid pressure at liquid line service
valve. Use a digital thermometer for all temperature
measurements. DO NOT use mercury or dial-type
thermometers.
3. Refer to Tables 6Aand 6B. Find temperature point at which
the required subcooling temperature intersects the mea-
sured liquid line pressure.
4. If the measured liquid line temperature does not agree
with the required liquid line temperature, ADD refriger-
ant to lower the temperature, or REMOVE refrigerant to
raise the temperature (allow a tolerance of±3F).
Table 4A Superheat Charging Table English
(Superheat Entering Suction Service Valve)
OUTDOOR
TEMP (F)
INDOOR COIL ENTERING AIR (F) WB
50 52 54 56 58 60 62 64 66 68 70 72 74 76
55 9 12141720232629323537404245
60 7 10121518212427303335384043
65 * 6 10 13 16 19 21 24 27 30 33 36 38 41
70 * * 71013161921242730333639
75 * * * 6 9 12 15 18 21 24 28 31 34 37
80 **** 581215182125283135
85 ****** 811151922263033
90 ****** 59131620242731
95 ******* 6101418222529
100 ******** 81215202327
105 ******** 5913172226
110 ********* 611152025
115 ********** 8141823
LEGEND
WB Wet Bulb
*Do not attempt to charge system under these conditions or refrig-
erant slugging may occur.
Table 4B Superheat Charging Table SI
(Superheat Entering Suction Service Valve)
OUTDOOR
TEMP (C)
INDOOR COIL ENTERING AIR (C) WB
10 11 12 13 14 16 17 18 19 20 21 22 23 24
13 5 7 8 9 11 13 14 16 18 19 21 22 23 25
16 4 6 7 8 10 12 13 15 17 18 19 21 22 24
18 * 3679111213151718202123
21 ** 46791112131517182022
24 *** 357810121316171921
27 **** 3478101214161719
29 ****** 4681112141718
32 ****** 357911131517
35 ******* 36810121416
38 ******** 478111315
41 ******** 35791214
43 ********* 3681114
46 ********** 481013
LEGEND
WB Wet Bulb
*Do not attempt to charge system under these conditions or refrig-
erant slugging may occur.
Table 5A — Required Suction-Tube Temperature (F)
English (Entering Suction Service Valve)
SUPERHEAT
TEMP (F)
SUCTION PRESSURE AT SERVICE PORT (psig)
61.5 64.2 67.1 70.0 73.0 76.0 79.2 82.4 85.7
0 35 36 39 41 43 45 47 49 51
2 37 39 41 43 45 47 49 51 53
4 39 41 43 45 47 49 51 53 55
6 41 43 45 47 49 51 53 55 57
8 43 45 47 49 51 53 55 57 59
10 45 47 49 51 53 55 57 59 61
12 47 49 51 53 55 57 59 61 63
14 49 51 53 55 57 59 61 63 65
16 51 53 55 57 59 61 63 65 67
18 53 55 57 59 61 63 65 67 69
20 55 57 59 61 63 65 67 69 71
22 57 59 61 63 65 67 69 71 73
24 59 61 63 65 67 69 71 73 75
26 61 63 65 67 69 71 73 75 77
28 63 65 67 69 71 73 75 77 79
30 65 67 69 71 73 75 77 79 81
32 67 69 71 73 75 77 79 81 83
34 69 71 73 75 77 79 81 83 85
36 71 73 75 77 79 81 83 85 87
38 73 75 77 79 81 83 85 87 89
40 75 77 79 81 83 85 87 89 91
Table 5B — Required Suction-Tube Temperature (C)
SI (Entering Suction Service Valve)
OUTDOOR
TEMP (C)
SUCTION PRESSURE AT SERVICE PORT (kPa)
424 443 463 483 503 524 546 568 591
0 2345678911
1 34567891112
2 456789111213
3 5678911121314
4 67891112131415
6 7 8 9 11 12 13 14 15 16
7 8 9 11 12 13 14 15 16 17
8 91112131415161718
9 11 12 13 14 15 16 17 18 19
10 12 13 14 15 16 17 18 19 21
11 13 14 15 16 17 18 19 21 22
12 14 15 16 17 18 19 21 22 23
13 15 16 17 18 19 21 22 23 24
14 16 17 18 19 21 22 23 24 25
16 17 18 19 21 22 23 24 25 26
17 18 19 21 22 23 24 25 26 27
18 19 21 22 23 24 25 26 27 28
19 21 22 23 24 25 26 27 28 29
20 22 23 24 25 26 27 28 29 31
21 23 24 25 26 27 28 29 31 32
22 24 25 26 27 28 29 31 32 33
9