Carrier 38EYA Heat Pump User Manual


 
INSTALLATION
IMPORTANT: Specifications for this unit in residential new
construction market require using the outdoor unit, indoor unit,
refrigerant tubing sets, metering device, and filter drier listed in
presale literature. There can be no deviation. Consult the Appli-
cation Guideline and Service Manual for Residential Split-System
Air Conditioners and Heat Pumps using Puron® Refrigerant to
obtain required unit changes for specific applications and for R-22
retrofit.
Step 1Check Equipment and Job Site
UNPACK UNIT
Move to final location. Remove carton taking care not to damage
unit.
INSPECT EQUIPMENT
File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit corner
panel. It contains information needed to properly install unit.
Check rating plate to be sure unit matches job specifications.
Step 2Install On a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern in Fig. 3
to determine base pan size and knockout hole location.
On rooftop applications, mount on level platform or frame. Place
unit above a load-bearing wall and isolate unit and tubing set from
structure. Arrange supporting members to adequately support unit
and minimize transmission of vibration to building. Consult local
codes governing rooftop applications.
Do not allow POE lubricant to come into contact with roofing
material. POE may determine certain types of synthetic
roofing.
Roof mounted units exposed to winds above 5 mph may require
wind baffles. Consult the Application Guideline and Service
Manual for Residential Split-System Air Conditioners and Heat
Pumps using Puron® Refrigerant for wind baffle construction.
NOTE: Unit must be level to within ± 2° 3/8 in./ft) per
compressor manufacturer specifications.
Step 3Clearance Requirements
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 30-in. clearance to
service end of unit and 48 in. above unit. For proper airflow, a 6-in.
clearance on 1 side of unit and 12 in. on all remaining sides must
be maintained. Maintain a distance of 24 in. between units.
Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.
On rooftop applications, locate unit at least 6 in. above roof
surface.
Step 4Operating Ambients
The minimum outdoor operating ambient in cooling mode without
additional accessories is 55°F, and the maximum outdoor operat-
ing ambient in cooling mode is 125°F. The maximum outdoor
operating ambient in heating mode is 66°F.
Fig. 2Connecting Tubing Installation
A94028
INSULATION
VAPOR TUBE
LIQUID TUBE
OUTDOOR WALL INDOOR WALL
LIQUID TUBE
VAPOR TUBE
INSULATION
CAULK
Avoid contact between tubing and structureNOTE:
THROUGH THE WALL
HANGER STRAP
(AROUND VAPOR
TUBE ONLY)
JOIST
1 MIN.
SUSPENSION
Fig. 3Mounting Unit to Pad
DIMENSIONS (IN.)
UNIT
SIZE
MINIMUM
MOUNTING PAD
DIMENSIONS
TIEDOWN KNOCKOUT
LOCATIONS
ABC
018, 024, 030 22-1/2 X 22-1/2 3-11/16 18-1/8 14-3/8
036060 30 X 30 6-1/2 23-1/2 20
A94199
C
B
A
3
8
D. (9.53) TIEDOWN
KNOCKOUTS (2) PLACES
2