Table 2 — 38AP060-100 Unit Physical Data — English
LEGEND
*Typical operating charge with 25 ft of interconnecting piping. Operating
charge is approximate for maximum system capacity. Unit is factory supplied
with nitrogen holding charge. Refrigerant charge for dual circuit units is the
total for both circuits.
†Maximum vertical separation between evaporator coil and condensing unit if
condensing unit is below the evaporator.
38AP UNIT SIZE 060 070 080 090 100
NOMINAL CAPACITY, 50/60Hz (tons) 50/60 58/70 67/80 75/90 83/100
CIRCUIT Dual Dual Dual Dual Dual
OPERATING WEIGHTS (lb)
Standard 2227 2450 2610 2835 2844
With Low Sound Option 2299 2522 2700 2943 2952
APPROXIMATE REFRIGERANT CHARGE,
TYPICAL (lb)*
60 70 78 96 100
NITROGEN SHIPPING CHARGE 15 psig
COMPRESSOR
hp (Qty) (CKT A/CKT B)
13 (2)/15 (2) 15 (2)/11 (3) 15 (2)/15 (3) 13 (3)/15 (3) 15 (3)/15 (3)
CAPACITY STEPS
Standard 45566
Digital Option 44 55 55 66 66
CRANKCASE HEATER (W) (each compressor) 90
CONDENSER FANS
Standard Propeller Type - Direct Drive
Quantity 44566
RPM 1140 (60 Hz), 950 (50 Hz)
Diameter (in.) 30
Total Watts (60 Hz) 6200 6000 7500 9000 9000
Total Watts (50 Hz) 5150 5000 6250 7500 7500
Low Noise
Shrouded Axial Fan - Direct Drive
Quantity 44566
RPM
850 (60 Hz), 700 (50 Hz)
Diameter (in.) 30
Total Watts (60 Hz) 5200 5000 6250 7500 7500
Total Watts (50 Hz) 4300 4150 5200 6250 6250
CONDENSER COIL MCHX Type
No. Coils per Circuit 1 2 2 to 3 3 3
sq ft 67.8 99.6 124.5 149.4 149.4
TEMPERATURE RELIEF Fusible Plug on Liquid Lines of Each Circuit - 210 F
CONNECTIONS (in.) ODF (CKT A/CKT B)
Suction Line 1
5
/
8
/ 1
5
/
8
1
5
/
8
/ 2
1
/
8
1
5
/
8
/ 2
1
/
8
2
1
/
8
/ 2
1
/
8
2
1
/
8
/ 2
5
/
8
Liquid Line
5
/
8
/
7
/
8
7
/
8
/
7
/
8
7
/
8
/
7
/
8
7
/
8
/
7
/
8
7
/
8
/
7
/
8
MAXIMUM HEIGHT FOR 3° F SUBCOOLING
(ft)†
75 75 75 75 75
CAPACITY PER CIRCUIT (%) (CKT A/CKT B) 46/54 47/53 40/60 46/54 50/50
MINIMUM UNIT CAPACITY (%) 23 24 20 15 17
MCHX — Microchannel Heat Exchanger
ODF — Outside Diameter, Female