Carrier 38APS025-050 Air Conditioner User Manual


 
25
Table 8 — Requirements for Installation of Liquid Line Solenoid Valve
38AP UNIT
SIZE
CIRCUIT
MAXIMUM ALLOWABLE EVAPORATOR SURFACE AREA
WITHOUT LIQUID LINE SOLENOID VALVE (sq ft)
4-Row,
1
/
2
in. Tube 6-Row,
1
/
2
in. Tube 8-Row,
1
/
2
in. Tube 3-Row,
3
/
8
in. Tube 4-Row,
3
/
8
in. Tube
025
Circuit A 18.9 12.7 9.5 36.1 28.1
Circuit B 18.9 12.7 9.5 36.1 28.1
Single Circuit 37.9 25.3 18.9 72.3 56.3
027
Circuit A 21.7 14.5 10.9 41.4 32.3
Circuit B 25.6 17.1 12.8 48.9 38.1
Single Circuit 47.3 31.6 23.7 90.3 70.4
030
Circuit A 21.7 14.5 10.9 41.4 32.3
Circuit B 25.6 17.1 12.8 48.9 38.1
Single Circuit 47.3 31.6 23.7 90.3 70.4
040
Circuit A 47.3 31.6 23.7
Circuit B 47.3 31.6 23.7
Single Circuit 94.7 63.3 47.3
050
Circuit A 47.3 31.6 23.7
Circuit B 47.3 31.6 23.7
Single Circuit 94.7 63.3 47.3
060
Circuit A 47.3 31.6 23.7
Circuit B 47.3 31.6 23.7
070
Circuit A 69.7 46.6 34.9
Circuit B 69.7 46.6 34.9
080
Circuit A 69.7 46.6 34.9
Circuit B 104.6 69.9 52.3
090
Circuit A 104.6 69.9 52.3
Circuit B 104.6 69.9 52.3
100
Circuit A 104.6 69.9 52.3
Circuit B 104.6 69.9 52.3
Fig. 17 — Long Line Option Kit Installation
a38-7119
NOTE: Locate long line kit as close to the
condensing unit as possible.