New Buck Corporation 91 Fan User Manual


 
FIGURE 1
FIREPLACE INSERT
30"
20"
15"
20"
8"
24"
HEARTH EXTENSION
MANTEL
INSTALLATION (Fireplace Insert)
Minimum Clearances to Combustible Materials (in inches)
TRIM PANELS
OPTION (B) OPTION (C)
SEAL TRIM PANELS
WITH INSULATION /
AND OR HIGH TEM-
PERATURE CAULK
REMOVE
DAMPER
OR WIRE IT
OPEN
AIRTIGHT
INSULATED
CLEAN-OUT
BLOCK-OFF PLATE
OR DAMPER
ADAPTER
STAINLESS
STEEL
CHIMNEY
CONNEC-
TOR MUST
EXTEND 1’
PAST THE
BLOCK-OFF
PLATE OR
TO THE
FLUE LINER
NOTE: Follow installation
instruction with Positive
Connection Kit.
(Kit sold separately)
NOTE: Follow installation instruction
with Direct Connection Kit.
(Kit sold separately)
CAP(PREVENTS
WATER FROM
ENTERING)
INSTALL A NON-COMBUSTIBLE
COVER PLATE TO PREVENT
WATER FROM ENTERING THE
CHIMNEY
FLUE
LINER
THE LINER MUST
BE STAINLESS
STEEL CONNEC-
TOR OR FLEXIBLE
VENT. FOLLOW
THE LINER MANU-
FACTURE’S IN-
STRUCTIONS FOR
INSTALLATION
AND SUPPORT.
AIRTIGHT
INSULATED
CLEAN-OUT
REMOVE
DAMPER
OR WIRE
IT OPEN