Bryant 593C Air Conditioner User Manual


 
5
SPECIFICATIONS Continued
* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.
If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).
The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors per the NEC (ANSI/NFPA 70) Article
336-26. If other than uncoated (non-plated), 60° or 75°C (140° or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for
larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
** Fan motor with ball bearings required. See Low-ambient controller Installation Instructions for application.
NOTE: Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.
UNIT SIZE 042-C, D 048-C 060-C
Operating Weight (Lb) 206 199 217
ELECTRICAL
Unit VoltsHertzPhase 208230601
Operating Voltage Range* 197253
Compressor Rated Load Amps 19.0 24.4 28.8
Locked Rotor Amps 105.0 140.0 165.0
Condenser Fan MotorFull Load Amps 1.4 1.4 1.4
Min Unit Ampacity for Wire Sizing 25.2 31.9 37.4
Min Wire Size (75°C Copper) AWG 10 10 8
Min Wire Size (60°C Copper) AWG 10 8 8
Max Wire Length (Ft) (75°C Copper) 73 59 78
Max Wire Length (Ft) (60°C Copper) 77 97 82
Max Branch Circuit Fuse Size** 40 50 60
COMPRESSOR and REFRIGERANT
CompressorManufacturer and Type Copeland Reciprocating Millennium Scroll Millennium Scroll
Temperature and Current Protection Internal Line Break Internal Line Break and Dome Thermostat
RefrigerantType and Amount (Lb)†† R-22 and 5.51 R-22 and 7.63 R-22 and 10.63
CONDENSER COIL and FAN
Coil Face (Sq Ft) 12.2 15.2 18.3
Fins per In.RowsCircuits 201225132514
Fan MotorHP, Type, and RPM 1/4 PSC and 1100
VoltsHertzPhase 208/230601
Condenser Airow (CFM) 3000
OPTIONAL EQUIPMENT
Support Feet KSASF0101AAA
Coastal Filter KAACF0801MED
Time Delay Relay KAATD0101TDR
Cycle Protector KSACY0101AAA
Crankcase Heater Standard KAACH1201AAA
Start AssistCapacitor/Relay Type KSAHS1301AAA KSAHS1601AAA
Start AssistPTC Type KAACS0201PTC
Sound Hood KSASH1201COP KSASH2001CYL
TXV Kit (RPB) KAATX0501RPB KAATX0601RPB KAATX0701RPB
TXV Kits (Hard Shutoff) KSATX0601HSO KSATX0701HSO
Low-Pressure Switch KAALP0101LPS
High-Pressure Switch KSAHI0101HPS
Filter Drier P502-8163S (RCD)
Evaporator Freeze Thermostat** KAAFT0101AAA
Liquid-Line Solenoid Valve KAALS0101LLS
Winter Start Control** KAAWS0101AAA
Low-Ambient Kit KSALA0201R22
MotorMaster® Control†† 32LT660004 (RCD)
Ball Bearing Fan Motor HC40GE232 (RCD)
Thermostat, Auto Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool TSTATBBNAC01-B
Thermostat, Auto Changeover,
7-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool TSTATBBPAC01-B
Builders Thermostat, Manual
Changeover, Non-Programmable,
°F/°C, 1-Stage Heat, 1-Stage Cool TSTATBBBAC01-B
Thermidistat ControlProgrammable/
Non-Programmable Thermostat with
Humidity Control TSTATBBPRH01-B
Outdoor Air Temperature Sensor TSTATBBSEN01-B
Backplate for Non-Programmable
Thermostat TSTATXXNBP01
Backplate for Programmable Thermostat TSTATXXPBP01
Backplate for Builders Thermostat TSTATXXBBP01
Thermostat Conversion Kit (4 to 5 wire)
10 Pack TSTATXXCNV10