Table 12 — Dry-Coil Air Delivery* — Downflow Discharge at 230 and 460 V — Unit 588A
(Deduct 10% from Cfm and Watts for 208 V Operation)
UNIT
588A
MOTOR
SPEED
AIR
DELIVERY
EXTERNAL STATIC PRESSURE (in. wg)
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
018
Low
Watts † 295 251 223 201 176 149 124 † † †
Cfm † 821 817 753 665 536 343 164 † † †
High
Watts 401 376 346 322 294 272 250 229 219 † †
Cfm 1334 1253 1128 996 816 658 461 246 167 † †
024,
030
Low
Watts † 285 284 282 278 274 270 261 251 244 230
Cfm † 798 761 727 682 634 581 525 450 371 304
Med
Watts † 378 371 368 362 357 343 332 315 301 283
Cfm † 1011 982 948 906 858 771 703 597 492 387
High
Watts † 520 511 487 472 451 431 411 385 362 341
Cfm † 1342 1309 1237 1181 1106 1007 892 745 610 471
036
Low
Watts † 460 439 423 398 379 349 322 297 270 246
Cfm † 1191 1136 1081 1005 907 795 687 579 471 349
Med
Watt † 511 492 470 450 420 392 364 332 308 275
Cfm † 1316 1244 1178 1104 1005 891 784 657 535 389
High
Watts † 655 631 603 584 552 522 492 459 433 398
Cfm † 1541 1458 1367 1292 1178 1053 920 806 662 509
042
Low
Watts † 637 612 587 560 526 493 455 † † †
Cfm † 1500 1450 1405 1350 1290 1200 1105 † † †
High
Watts † 790 750 700 679 639 608 574 547 † †
Cfm † 1750 1675 1604 1509 1421 1323 1221 1094 † †
048
Low
Watts † 847 784 746 708 646 609 563 516 † †
Cfm † 1995 1901 1822 1730 1580 1477 1319 1178 † †
High
Watts † † 909 852 820 801 751 687 639 † †
Cfm † † 2018 1896 1814 1729 1582 1380 1270 † †
060
Low
Watts † 983 950 923 885 845 804 751 697 665 633
Cfm † 1838 1808 1755 1702 1628 1553 1446 1339 1257 1175
Med
Watts † 1115 1083 1045 1006 964 921 872 823 783 742
Cfm † 2067 2023 1957 1891 1807 1723 1612 1501 1392 1282
High
Watts † 1284 1201 1166 1131 1092 1053 1001 950 907 864
Cfm † 2167 2108 2038 1968 1882 1796 1676 1555 1437 1318
*Air delivery values are without air filter and are for dry coil. See
Table 17 for wet coil pressure drop. Deduct field-supplied air filter
pressure drop and wet coil pressure drop to obtain external static
pressure available for ducting.
†Unit air delivery is outside of operating range.
NOTE: Do not operate the unit at a cooling airflow that is less than
350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-
coil icing may occur at airflows below this point. Water blow-off may
occur at airflows above 450 cfm per 12,000 Btuh of rated cooling
capacity.
Table 13 — Dry-Coil Air Delivery* — Horizontal Discharge at 230 and 460 V — Unit 589A
(Deduct 10% from Cfm and Watts for 208 V Operation)
UNIT
589A
MOTOR
SPEED
AIR
DELIVERY
EXTERNAL STATIC PRESSURE (in. wg)
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
024,
030
Low
Watts 280 275 265 255 250 245 240 ††††
Cfm 820810755700660600560††††
Med
Watts 365 360 350 345 340 330 320 310 300 † †
Cfm 1025 1010 975 940 900 850 800 720 630 † †
High
Watts † † 490 480 470 460 445 430 410 390 380
Cfm † † 1300 1255 1200 1150 1080 1005 915 790 620
036
Low
Watts 520 495 474 458 445 425 †††††
Cfm 1375 1335 1290 1240 1200 1140 †††††
Med
Watts 575 560 535 510 480 460 440 425 † † †
Cfm 1520 1490 1450 1400 1380 1300 1200 1080 † † †
High
Watts ††††650614575540510480†
Cfm ††††1560 1500 1380 1280 1170 1060 †
042
Low
Watts 490 480 470 460 450 430 410 390 † † †
Cfm 1400 1380 1340 1300 1250 1200 1140 1070 † † †
Med
Watts 590 580 560 545 525 505 480 450 420 † †
Cfm 1600 1560 1540 1470 1430 1360 1300 1220 1120 † †
High
Watts †††††700670640600560500
Cfm †††††1780 1670 1600 1480 1340 1100
048**
Low
Watts 1050 1000 970 930 870 810 750 680 600 † †
Cfm 1850 1830 1800 1785 1750 1700 1640 1500 1330 † †
High
Watts † † † 1050 1000 930 870 810 740 665 †
Cfm † † † 2000 1940 1850 1750 1635 1500 1300 †
*Air delivery values are without air filter and are for dry coil. See
Table 17 for wet coil pressure drop. Deduct field-supplied air filter
pressure drop and wet coil pressure drop to obtain external static
pressure available for ducting.
†Unit air delivery is outside of operating range.
**For 460 v units only.
NOTE: Do not operate the unit at a cooling airflow that is less than
350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-
coil icing may occur at airflows below this point. Water blow-off may
occur at airflows above 450 cfm per 12,000 Btuh of rated cooling
capacity.