Bryant 581J Air Conditioner User Manual


 
8
TABLE 2 – AHRI COOLING RATING TABLE 1--STAGE COOLING
UNIT
COOLING
STAGES
NOM.
CAPACITY
(TONS)
NET
COOLING
CAPACITY
(MBH)
TOTAL
POWER (kW)
SEER EER IEER
04A 1 3 36.0 2.9 15.00 12.50 N/A
05A 1 4 48.5 3.7 15.60 13.00 N/A
06A 1 5 57.5 4.6 15.20 12.45 N/A
07A 1 6 73.0 6.0 N/A 12.00 13.00
TABLE 3 – AHRI COOLING RATING TABLE 2--STAGE COOLING
UNIT
COOLING
STAGES
NOM.
CAPACITY
(TONS)
NET
COOLING
CAPACITY
(MBH)
TOTAL
POWER (kW)
SEER EER IEER
08D 2 7.5 89.0 7.4 N/A 12.00 13.00
09D 2 8.5 97.0 8.1 N/A 12.00 13.00
LEGEND
AHRI --- Air Conditioning, Heating and Refrigeration
Institute Test Standard
ASHRAE --- American Society of Heating, Refrigerating
and Air Conditio ning, Inc.
EER --- Energy Efficiency Ratio
IEER --- Integrated Energy Efficiency Ratio
SEER --- Seasonal Energy Efficiency Ratio
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
NOTES:
1. Rated in a ccordance w ith AHRI Standards 210/240
(04---06 size) and 340/360 (07---09 size).
2. Ratings are based on:
Cooling Standard: 80_F(27_C) db, 67_F(19_C) wb
indoor air temp and 95_F(35_C) db outdoor air temp.
IEER Standard: A measure that expresses cooling
part---load EER efficiency for co mmercial unitary air---
conditioning and heat pump equipment on the basis of
weighted operation at various load capacities.
3. All 581J units comply with ASHRAE 90.1 2001, 2004
Energy Standard for minimum SEER and EER
requirements.
4. 581J units comply with US Energy P olicy Act (2005).
To evaluate code compliance requirements, refer to
state and local codes or visit the following website:
http://bcap---energ y.org.
581J