CURBS & WEIGHTS DIMENSIONS -- 581J04--06 (cont.)
UNIT
STD. UNIT
WEIGHT
CORNER
WEIGHT (A)
CORNER
WEIGHT (B)
CORNER
WEIGHT (C)
CORNER
WEIGHT (D)
C.G. HEIGHT
LBS. KG. LBS. KG. LBS. KG. LBS. KG. LBS. KG. X Y Z
505 229 124 56 117 53 128 58 136 62 36 1/8 [918] 24 3/8 [619] 19 [483]
590 268 151 69 144 65 144 65 151 69 36 1/4 [921] 23 3/8 [594] 20 1/8 [511]
600 271 156 71 145 66 144 65 155 70 35 7/8 [911] 23 1/4 [591] 19 1/2 [495]
*- STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING.
FOR OTHER OPTINS AND ACCESSORIES REFER TO THE PRODUCT DATA CATALOG.
X
Y
CORNER A
CORNER B
CORNER C
CORNER D
TOP
Z
581J-04A
581J-05A
581J-06A
C10379
Fig. 2 -- Dimensions 581J04--06
C
B
A
D
C08337
Fig. 3 -- Service Clearance
LOC DIMENSION CONDITION
A
48” (1219 mm) Unit disconnect is mounted on panel
18” (457 mm) No disconnect, convenience outlet option
18” (457 mm) Recommended service clearance
12” (305 mm) Minimum clearance
B
42” (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall)
36” (914 mm) Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)
Special Check for sources of flue products within 10---ft of unit fresh air intake hood
C
36” (914 mm) Side condensate drain is used
18” (457 mm) Minimum clearance
D
48” (1219 mm) No flue discharge accessory installed, surface is combustible material
42” (1067 mm) Surface behind servicer is g rounded (e.g., metal, masonry wall, another unit)
36” (914 mm) Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)
Special Check for adjacent units or building fresh air intakes within 10---ft of this unit’s flue outlet