Bryant 581J Air Conditioner User Manual


 
20
CURBS & WEIGHTS DIMENSIONS -- 581J07--09 (cont.)
581J-07A
581J-09D
581J-08D
C10381
Fig. 6 -- Dimensions 581J07--09
C
B
A
D
C08337
Fig. 7 -- Service Clearance
LOC DIMENSION CONDITION
A
48” (1219 mm) Unit disconnect is mounted on panel
18” (457 mm) No disconnect, convenience outlet option
18” (457 mm) Recommended service clearance
12” (305 mm) Minimum clearance
B
42” (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall)
36” (914 mm) Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)
Special Check for sources of flue products within 10---ft of unit fresh air intake hood
C
36” (914 mm) Side condensate drain is used
18” (457 mm) Minimum clearance
D
48” (1219 mm) No flue discharge accessory installed, surface is combustible material
42” (1067 mm) Surface behind servicer is g rounded (e.g., metal, masonry wall, another unit)
36” (914 mm) Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)
Special Check for adjacent units or building fresh air intakes within 10---ft of this unit’s flue outlet
581J