Bryant 581J Air Conditioner User Manual


 
13
TABLE 9 – PHYSICAL DATA (HEATING) 3 -- 6 TONS
581J*04A 581J*05A 581J*06A 581J*07A
Gas Connection
#ofGasValves 1 1 1 1
Nat. gas supply line press (in. w.g.)/(PSIG) 4 --- 13 / 0.18 --- 0.47 4 --- 13 / 0.18 --- 0.47 4 --- 13 / 0.18 --- 0.47 4 --- 13 / 0.18 --- 0.47
Propane supply line press (in. w.g.)/(PSIG) 11 ---13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47 11 ---13 / 0.40 --- 0.47
Heat Anticipator Setting (Amps)
1st stage 0.14 0.14 0.14 0.14
2nd stage 0.14 0.14 0.14 0.14
Natural Gas, Propane Heat
#ofstages/#ofburners(total) 1or2/2 1or2/2 1or2/2 2/2
LOW
Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115
Temperatureriserange(F) 25 --- 55 25 --- 55 20 --- 55 15 --- 55
#ofstages/#ofburners(total) 1or2/3 1or2/3 1or2/3 2/3
MED
Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 195 / 115
Temperatureriserange(F) 55 --- 85 35 --- 65 30 --- 65 20 --- 50
Connection size --- 1or2/3 1or2/3 2/4
HIGH
#ofstages/#ofburners(total) --- 1/2” NPT 1/2” NPT 3/4” NPT
Rollout switch opens / closes --- 195 / 115 195 / 115 195 / 115
Temperatureriserange(F) --- 50 --- 80 40 --- 80 30 --- 60
Low N O
x
Gas Heat
#ofstages/#ofburners(total) 1or2/2 1or2/2 1or2/2 ---
LOW
Connection size 1/2” NPT 1/2” NPT 1/2” NPT ---
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 ---
Temperatureriserange(F) 20 --- 50 20 --- 50 15 --- 50 ---
#ofstages/#ofburners(total) 1or2/3 1or2/3 1or2/3 ---
MED
Connection size 1/2” NPT 1/2” NPT 1/2” NPT ---
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 ---
Temperatureriserange(F) 30 --- 60 30 --- 60 25 --- 60 ---
---
#ofstages/#ofburners(total) --- 1or2/3 1or2/3 ---
HIGH
Connection size --- 1/2” NPT 1/2” NPT ---
Rollout switch opens / closes --- 195 / 115 195 / 115 ---
Temperatureriserange(F) --- 40 --- 70 35 --- 70 ---
581J