HEAT PUMP HEATING PERFORMANCE CONTINUED
INDOORAIR
OUTDOORCOILENTERINGAIRTEMPERATURES°F( °C)
---3 (---19.4) 7(---13.9) 17(---8.3) 27(---2.8) 37(2.8) 47(8.3) 57 (13.9) 67(19.4)
EDB
°F(°C)
CFM
Capacity M Btuh
Total
Sys.
KW†
Capacity M Btuh
Total
Sys.
KW†
Capacity M Btuh
Total
Sys.
KW†
Capacity M Btuh
Total
Sys.
KW†
Capacity M Btuh
Total
Sys.
KW†
Capacity M Btuh
Total
Sys.
KW†
Capacity M Btuh
Total
Sys.
KW†
Capacity M Btuh
Total
Sys.
KW†
Total Integ* Total Integ* Total Integ* Total Integ* Total Integ* Total Integ* Total Integ* Total Integ*
213ANA060---D OutdoorSection With FY4ANB060IndoorSection
65
(18.3)
1750 24.06 22.14 2.98 30.37 27.90 3.14 37.01 33.74 3.31 44.09 39.16 3.49 51.99 47.31 3.70 60.58 60.58 3.88 68.82 68.82 4.11 77.46 77.46 4.36
2000 24.32 22.37 2.95 30.63 28.14 3.10 37.33 34.04 3.24 44.47 39.50 3.41 52.57 47.84 3.59 60.71 60.71 3.75 68.81 68.81 3.94 75.63 75.63 4.11
2250 24.52 22.56 2.93 30.87 28.37 3.06 37.59 34.27 3.20 44.78 39.77 3.35 53.02 48.24 3.50 60.66 60.66 3.65 68.43 68.43 3.82 72.29 72.29 3.89
70
(21.1)
1750 23.20 21.34 3.13 29.59 27.19 3.31 36.29 33.09 3.49 43.39 38.54 3.68 51.21 46.60 3.91 59.77 59.77 4.10 67.95 67.95 4.33 76.55 76.55 4.60
2000 23.45 21.58 3.10 29.88 27.46 3.27 36.63 33.40 3.42 43.77 38.87 3.60 51.69 47.04 3.80 60.02 60.02 3.96 68.06 68.06 4.16 75.59 75.59 4.36
2250 23.66 21.77 3.08 30.11 27.67 3.23 36.88 33.62 3.38 44.07 39.14 3.54 52.16 47.47 3.70 60.03 60.03 3.86 67.84 67.84 4.04 72.73 72.73 4.14
75
(23.9)
1750 22.27 20.49 3.29 28.76 26.42 3.48 35.52 32.38 3.67 42.68 37.91 3.88 50.42 45.89 4.12 58.93 58.93 4.32 67.07 67.07 4.57 75.59 75.59 4.84
2000 22.53 20.73 3.26 29.05 26.70 3.44 35.84 32.68 3.61 43.07 38.25 3.80 50.92 46.34 4.01 59.25 59.25 4.18 67.27 67.27 4.39 75.25 75.25 4.61
2250 22.74 20.92 3.24 29.29 26.92 3.41 36.12 32.93 3.56 43.36 38.51 3.74 51.40 46.77 3.92 59.39 59.39 4.07 67.19 67.19 4.26 72.81 72.81 4.39
HEATINGINDOOR
MODEL
CAPACITY POWER FURNACEMODEL
*FY4ANB060 1.00 1.00
FE4ANB006 0.98 0.94
FV4BNB006 0.98 0.94
FX4CN(B,F)060 0.99 0.96
CAP**6021A** 0.99 0.99
CAP**6024A** 0.99 0.99
CNPH*6024A** 1.00 1.01
CNPV*6024A** 1.00 1.01
CSPH*6012A** 1.00 0.99
CAP**6021A** 0.99 0.99 315(A,J)AV060110
CNPH*6024A** 0.99 1.00 315(A,J)AV060110
CSPH*6012A** 1.00 0.99 315(A,J)AV060110
CAP**6024A** 0.98 0.98 315(A,J)AV066135
CNPH*6024A** 0.99 1.00 315(A,J)AV066135
CNPV*6024A** 0.99 1.00 315(A,J)AV066135
HEATINGINDOOR
MODEL
CAPACITY POWER FURNACEMODEL
CSPH*6012A** 0.99 0.97 315(A,J)AV066135
CAP**6024A** 0.98 0.97 315(A,J)AV066155
CNPH*6024A** 0.99 0.99 315(A,J)AV066155
CNPV*6024A** 0.99 0.99 315(A,J)AV066155
CSPH*6012A** 0.99 0.97 315(A,J)AV066155
CNPH*6024A** 0.99 1.03 353AAV048080
CSPH*6012A** 0.99 1.01 353AAV048080
CAP**6021A** 0.98 0.99 353AAV060100
CNPH*6024A** 0.99 1.01 353AAV060100
CSPH*6012A** 0.99 0.99 353AAV060100
CAP**6024A** 0.98 0.98 353AAV060120
CNPH*6024A** 0.98 0.99 353AAV060120
CNPV*6024A** 0.98 0.99 353AAV060120
CSPH*6012A** 0.99 0.98 353AAV060120
CAP**6021A** 0.99 1.01 355(A,C)AV060100
HEATINGINDOOR
MODEL
CAPACITY POWER FURNACEMODEL
CSPH*6012A** 1.00 1.01 355(A,C)AV060100
CAP**6024A** 0.99 1.01 355(A,C)AV060120
CNPH*6024A** 1.00 1.03 355(A,C)AV060120
CNPV*6024A** 1.00 1.03 355(A,C)AV060120
CSPH*6012A** 1.00 1.01 355(A,C)AV060120
CAP**6021A** 0.98 0.99 313*AV048090
CNPH*6024A** 0.99 1.01 313*AV048090
CSPH*6012A** 0.99 0.99 313*AV048090
CAP**6021A** 0.98 0.98 313*AV060110
CNPH*6024A** 0.99 1.00 313*AV060110
CSPH*6012A** 0.99 0.97 313*AV060110
CAP**6024A** 0.98 0.99 313*AV060135
CNPH*6024A** 0.99 1.01 313*AV060135
CNPV*6024A** 0.99 1.01 313*AV060135
CSPH*6012A** 0.99 0.98 313*AV060135
NOTE: When the required data falls between the published data, i nterpolation may be performed. Extrapolation is not an acceptable practice.
* TheBtuh heating capacityvaluesshownare net integratedvaluesfrom which the defrosteffect hasbeen subtracted.The Btuh heating from supplementheaters should be added t o those values to o btain total system capacity.
{ The kW values i nclude the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters s hould be a dded to these values to o btain total system kilowatts.
EDB —EnteringDryBulb
213A