Bryant 124A Air Conditioner User Manual


 
7
ELECTRICAL DATA
UNIT
SI Z E ---
SERIES
V/PH
OPER
VOLTS*
COMPR FAN
MCA
MIN
WIRE
SIZE{
MIN WIRE
SIZE{
MAX
LENGTH
ft. (m)}
MAX
LENGTH
ft. (m)}
MAX
FUSE**
or CKT
BRK
AMPS
MAX MIN LRA RLA FLA 60° C 75° C 60° C 75° C
018---C
208/230/1 253 197
48.0 9.0 0.5 11.7 14 14 67 (20.4) 64 (19.5) 15
024---D 58.3 13.5 0.5 17.3 14 14 46 (14.0) 43 (13.1) 30
030---D 73.0 14.1 0.5 18.1 14 14 44 (13.4) 41 (12.5) 30
036---C 79.0 16.7 1.2 22.0 12 12 57 (17.4) 54 (16.5) 35
042---D 112.0 17.9 1.2 23.6 12 10 53 (16.2) 50 (15.2) 40
048---C 117.0 21.8 1.2 28.4 10 10 70 (21.3) 67 (20.4) 40
060---C 134.0 26.4 1.2 34.2 8 8 91 (27.7) 86 (26.2) 50
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater tha n 30° C, consult table 310---16 of the NEC (ANSI/NFPA 70). The a mpacity of non---metallic---sheathed cable (N M),
trade name ROMEX, shall be that of 60° C conditions, per the NEC ( ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75° C
insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA
70).
} Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time ---Delay fuse.
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA ---RatedLoadAmps
NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2001 requirements of ASHRAE Standards 90.1
A--WEIGHTED SOUND POWER
U NI T S IZ E ---
VOLTAGE,
SERIES
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA , without tone adjustment)‘
125 250 500 1000 2000 4000 8000
018---C 73 56.0 60.0 65.0 69.0 63.0 60.0 52.5
024---D 74 51.0 60.0 66.5 66.5 64.0 60.0 52.5
030---D 74 53.0 62.0 68.5 69.0 65.5 61.0 54.0
036---C 72 52.0 62.0 65.5 67.5 63.0 61.0 53.5
042---D 74 60.0 65.5 68.5 68.5 65.0 60.0 52.5
048---C 73 59.5 63.5 66.5 67.5 64.0 62.0 55.5
060---C 74 55.5 64.0 67.0 69.0 65.0 60.0 54.5
NOTE: Tested in accordance with ARI Standard 270---95. (Not listed with ARI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE---VOLTAGE, SERIES REQUIRED SUBCOOLING _F(_C)
018---C 10 (5.6)
024---D 10 (5.6)
030---D 11 (6.1)
036---C 10 (5.6)
042---D 12 (6.7)
048---C 9 (5.0)
060---C 9 (5.0)
124A